Digital input/ output parameter group 03
PARAMETER DESCRIPTION 151
5.4.2 Digital output terminals function selection
Detect information generated and send digital signal output during inverter operation.
Parameter
Name
Default Setting Range
Content
03-10
P.40
Terminal SO1-SE
output function
1
0
RUN(Output when inverter running)
1
SU(Output when reach target frequency)
2
FU(Output when reach 03-21 03-22 value )
3
OL(Output when overload)
4
OMD(When the percentage of the output current is lower than
03-23 (P.62) and exceed (03-24 (P.63)) of time, OMD will
output)
5
ALARM(Output when alarm)
6
PO1(Output when in program operation step)
7
PO2(Output when in program operation cycle)
8
PO3(Output when in program operation pause)
9
BP(Output when use inverter output in function : switch between
inverter and commercial power-supply)
10
GP(Output when use commercial power-supply in function :
switch between inverter and commercial power-supply)
11
OMD1(When inverter reach target frequency and the
percentage of the output current is lower than 03-23 (P.62) and
exceed (03-24 (P.63))of time, OMD will output a signal)
12~15
Reserved
16
Output when cooling-fan is damaged
17
RY(Output when inverter is powered on and no alarm)
18
Output when it’s time for maintenance
19
OL2 (Output when overload 2)
20
Output when capacitor abnormal
21
Output when in position control reach position
22
Output when detect curl
in
tension control
23
Output when detect power marker
24~40
Reserved
41
PID feedback disconnection alarm(AEr)
03-11
P.85
Terminal A1-B1-C1
output function
5
Same as
03-10(P.40)
Same as 03-10(P.40)
03-12
P.129
Terminal SO2-SE
output function
2
Same as
03-10(P.40)
Same as 03-10(P.40)
03-13
P.130
Terminal A2-B2-C2
output function
0
Same as
03-10(P.40)
Same as 03-10(P.40)
Digital output terminals function selection
Terminal SO1 default value (03-10(P.40)) is 1 which means “SU”. If 03-10(P.40) value is changed, terminal
function will change as shown in table above.
Terminal SO2 default value (03-12)
(P.129) is 2 which means “FU”. If 03-12(P.129) value is changed, terminal
function will change as shown in table above.
Terminals SO1/SO2-SE are “open collector output.” Please refer to Section 3.7.
Terminal A1-B1-C1
default value (03-11(P.85))
is 5 which means “ALARM”. If 03-11(P.85) value is changed,
terminal function will change as shown in table above.
Terminal A2-B2-C2
default value (03-13(P.130)) is 0 which means “RUN”. If 03-13(P.130) value is changed,
terminal function will change as shown in table above.