Protection parameter group 06
PARAMETER DESCRIPTION 192
5.7.11 Maintenance alarm function
Inverter counts operation time and trigger maintenance alarm output signal after time set.
Parameter
Name
Default Setting Range
Content
06-17
P.261
Maintenance alarm
function
0
0
Off
1~9998day
Used to set the time for maintenance alarm output signal
Maintenance alarm function
If
digital output terminal (03-10~03-13(P.40,P.85,P.129~P.130),03-42~03-57(P.568~P.583)) is set to 18, it is the
maintenance alarm function. If the operating days of inverter reach set value of maintenance alarm time parameter
06-17(P.261), multi-function digital output terminal or multi-function relay of inverter will output a signal.
5.7.12 Short circuit to ground protection
Set
inverter detects short circuit to ground and detection level
Parameter
Name
Default
Setting Range
Content
06-18
P.280
Short circuit to ground
detection when
starting
0
0
Off
1
When given run command to inverter, inverter detects
short circuit to ground
06-19
P.282
GF detection level
when running
50.0%
0~100.0%
280K/315KF and below model:0~100.0%
70.0%
315K/355KF and above model:0~100.0%
Short circuit to ground
Short circuit to ground detection after power-on is set by 06-19(P.282).
06-18(P.280) is used to set whether check when start, 06-19(P.282) is also used to set during operation.
If 06-18(P.280) is set 1 and output short-circuited current exceeds 50% of rated current when start, inverter will
stop outputting and trigger GF alarm.
During operation, output short-circuited current exceeds
set value of 06-19(P.282) % rated current, inverter will
stop outputting and trigger GF alarm.