General specification
INVERTER INTRODUCTION22
Protection mechanism /
alarm function
Protection mechanism/Alarm function: output short-circuit protection, over-current protection,
over-voltage protection, under voltage protection, motor over-heat protection, IGBT module
over-heat protection, cooling fun abnormal, communication abnormal protection, PU
communication port peripheral devices abnormal protection, memory exception protection, PID
abnormal protection, CPU abnormal protection, stall prevention abnormal protection,
short-circuit over-current protection, over-torque abnormal protection, brake crystal abnormal
protection, power input abnormal protection, 4-5/3-5 terminal abnormal protection, PG card
communication error protection, encoder mode abnormal protection, PG card feedback signal
abnormal protection, speed deviation excess protection when in closed-loop control, material
disconnection protection, Z phase pulse loss protection, Z phase noise detection protection,
reverse rotation detection protection, anti-reverse rotation detection protection, relay operation
abnormal protection, safety circuit abnormal protection, to earth leakage current protection,
hardware detection circuit abnormal protection, three-phase current sampling circuit abnormal
protection, expansion card SLOT1 abnormal protection, expansion card SLOT2 abnormal
protection, expansion card SLOT3 abnormal protection
Environment
Ambient
temperature
Heavy duty:-10 ~ +50℃ (non-freezing), Light duty:-10 ~ +40℃ (non-freezing), please refer
to 3.4.5 Class of protection and operation temperature for details.
Ambient humidity Below 90%Rh (non-condensing).
Storage
temperature
-20 ~ +65℃.
Surrounding
environment
Indoor, no corrosive gas, no flammable gas, no flammable powder.
Altitude
Altitude below 3000 meters, when altitude is above 1,000 moderate the rated current 2% per
100 m
Note 1: According to the safety regulation EN61800-5-1, which is required to declare in CE
certification, this series of inverters can be installed in an environment of over-voltage class II
when the altitude is less than 3000m. When the altitude is less than 2000m, can be installed in
harsher conditions that meet the requirements of over-voltage class III.
Vibration
Vibration below 5.9 m/s
2
(0.6G).
Grade of protection
Frame A, B,C,IP20 / NEMA TYPE 1, Frame D and above IP00 / UL OPEN TYPE (optional IP20
accessories can be added).
The degree of
environmental
pollution
2
Class of protection Class I
International certification
CE
*1: Even if the frequency related parameter setting is greater than 599Hz, the actual output frequency upper limit is still
599Hz.