System parameter group 00
PARAMETER DESCRIPTION 93
RESET
STOP
button function selection
Press
RESET
STOP
button to stop during operation (00-14
(
P.75
)
=“1”
)
Note:
When running in non-PU and H2 modes, pressing the
RESET
STOP
button will display E0 and lock all
functions on the keypad. Please follow the steps below to cancel this state
:
1.
If the start signal is given from digital input terminal, switch off the signal (Note1);
2.
Press
RESET
STOP
button for over 1.0 second to remove E0 state.
No matter which mode inverter is in, press
RESET
STOP
button for over 1.0 second will reset the inverter after alarm
occurs.
Note: 1. In programmed operation mode, it is not necessary to switch off the start signal. Inverter will run at the section
where it stopped after reset.)
2. After resetting, the values of “electronic thermal relay” and “IGBT module thermal relay” will be set to zero.
5.1.8 Forward/reverse rotate prevent function
Set this parameter to limit the motor rotation to only one direction, and prevent reverse rotation fault resulting from
the incorrect input of the start signal.
Parameter
Name
Default
Setting Range
Content
00-15
P.78
Prevent forward/
reverse rotation
selection
0
0
Forward/reverse rotation are both permitted.
1
Prevent reverse rotation (Giving reverse signal
decelerates and stops the motor).
2
Prevent forward rotation (Giving forward signal
decelerates and stops the motor).
Note: It is valid to all start signals.