Basic parameter group 01
PARAMETER DESCRIPTION 109
5.2.7 JOG run
The frequency and acceleration/deceleration time for JOG running can be set. JOG can be used for conveyor
positioning, test run, etc.
Parameter
Name
Default Setting Range
Content
01-13
P.15
JOG frequency
5.00Hz
0~650.00Hz
Set the frequency during fixed point motion
01-14
P.16
JOG acceleration/
deceleration time
0.50s
0~360.00s/
0~3600.0s
01-08(P.21)=0/
01-08(P.21)=1
JOG operation
In JOG mode, the output frequency is the set value of 01-13(P.15), and the acceleration / deceleration time is the
set value of 01-14(P.16).
01-14
(P.16 )
01-09
(P.20)
01-03
(P.15)
01-03
(P.15)
01-09
(P.20)
01-14
(P.16 )
Forward
rotation
Reverse
rotation
Press
FWD
Press
REV
Output frequency
Time
Note: Please refer to Section 4.3.3 for how to enter the JOG mode.
Setting