Application parameter group 10
PARAMETER DESCRIPTION 265
10-38(P.278) is the switch frequency between deceleration time during input power failure 1 and deceleration time
during input power failure 2; If 10-37(P.277) is not set, motor will still decelerates for the time set to 10-36(P.276).
10-39(P.279) is UV avoidance voltage gain when 10-33 set to 11 or 12; if 10-33(P.273)=1 or 2, 10-39(P.279) is
invalid.
under-voltage avoidance function(10-33(P.273)=”11”,”12”):
When setting 10-33(P.273)=”11” or “12”, frequency is decreased to prevent an under-voltage from occurring
during deceleration at input power fail.
Frequency drop trend and responsiveness can be adjusted by 10-39(P.279). If the set value is larger, the
response to bus voltage changes will be better. However, if the load inertia is large, the regenerative energy will
also be large, so 10-39(P.279) should be set smaller at this time.
Note: 1.This function is only for V/F control mode.
2.This function won’t work when using DC bus power supply
5.11.13 VF complete separation
Voltage command given mode, voltage acceleration/deceleration time and voltage deceleration mode in VF
complete separation.
Parameter
Name
Default
Setting Range
Content
10-40
P.700
VF separated voltage
source
0
0
Given by digital 10-41(P.701).
1
Given by analog or HDI pulse.
10-41
P.701
VF separated voltage
digital
380/440V
0~440V
440V voltage
50Hz (when 00-24=1) / 60Hz (when
00-24=0) system setting
220V
0~220V
220Vvoltage
10-42
P.702
VF separated voltage
Acc time
0.0s
0~1000.0s
Time for voltage accelerating from 0 to motor rated voltage.
10-43
P.703
VF separated voltage
Dec time
0.0s
0~1000.0s
Time for voltage decelerating from motor rated voltage to 0.
10-44
P.704
VF separated Stop
selection
0
0
Frequency/voltage independently decreases to 0.
1
After the voltage decreases to 0, frequency decreases.
VF complete separation
Parameter 10-40(P.700)~10-44(P.704) are valid only when 01-12(P.14)=14. VF complete separation is normally
used in induction heating, inverse power supply and torque motor control.
The voltage source for V/F complete separation is set in the same way as the frequency source, it can be set by
digital or external analog terminal or HDI terminal.