Appendix 1 Parameter table
APPENDIX 367
Group
Parameter
Number
Name
Setting Range
Default
Page
03-00
P.83
Terminal STF input function
35: MPO (In “external mode” run manual cycle
operation.)
0
36: TRI(Triangle wave function)
37: GP_BP (Automatic switch between inverter
and commercial power-supply.)
38: CS(Manual switch to commercial power
supply)
39: STF/STR +STOP (Use with RUN signal,
when ON, motor runs reverse,
when OFF, motor stops then runs forward.)
40: P_MRS (Stops inverter output immediately
by pulse signal input)
41: PWM set frequency(Note 1)
42: Reserved
43: RUN_EN (Enable digital input terminal
operation)
44: PID_OFF (Enable digital input terminal
turning off PID)
45: Second mode
46: Initial roll radius selection 1
47: Initial roll radius selection 2
48: Thickness selection 1
49: Thickness selection 2
50: Winding unwinding switch
51: Pre-drive command
52: Save torque value
53: Save torque value enable
54: Revs counting signal (note1)
55: Speed/Torque control
switch
56: Roll radius reset
57: High-speed pulse input function (note1)
58: Analog terminal 2-5 high priority
59: Analog terminal 3-5 high priority
60: Built-in PLC start/stop
61: SHOM (Homing enable)
62: ORGP (Set homing point)
63: Position/Speed control switch
64: External zero-servo
switch
65: External accelerate/decelerate pause
66: External forced stop
67:Roll diameter calculation stop
68:Enable single point positioning
69:Enable multipoint positioning
70:Enable entire position control by pulse input
command
71:External torque command polarity reverse
99999:Off
03-01
P.84
Terminal STR input function
Same as 03-00(P.83)
1
03-02
P.86
Terminal RES input function
Same as 03-00(P.83)
30