Protection parameter group 06
PARAMETER DESCRIPTION 187
5.7.4 Decrease carrier protection setting
It selects decrease carrier or decrease rated current protection by setting parameters.
Parameter
Name
Default Setting Range
Content
06-07
P.263
Decrease carrier
protection setting
0
0
Fixed carrier frequency, and limit output current
according to
carrier value.
1
Fixed rated current, and limit carrier according to output
current and temperature.
Decrease carrier protection
06-07(P.263)=0, fixed carrier frequency, but the rated current of inverter will be reduced according to set carrier
frequency and corresponding curve, so as to avoid overheating of IGBT module on inverter:
Load (%)
Carrier (KHz)
:
0.75K~15K
Applicable frame below
:
440V type heavy duty (HD)
2 3 4 5 6 7 8 9 10 11 12 13 14 15
100
90
80
70
60
50
40
30
20
10
0
:
18.5K~75K
:
90K~315K
Load (%)
Carrier (KHz)
:
0.75K~15K
Applicable frame below
:
440V type normal duty (ND)
2 3 4 5 6 7 8 9 10 11 12 13 14 15
100
90
80
70
60
50
40
30
20
10
0
:
18.5K~75K
:
90K~315K
Setting