PID parameter group 08
PARAMETER DESCRIPTION 235
5.9.14 PID current feedback disconnection detection
When PID feedback is a current signal (4~20mA), it is used to detect feedback signal disconnection.
Param
eter
Name
Default
Setting range
Content
08-45
P.253
Feedback
disconnection detection
time
0.0s
0.0~600.0s
Set the time for the current feedback to break. When set to 0,
the current feedback detection function is invalid
08-46
P.254
Feedback
disconnection
processing method
0
0
AEr alarm, inverter free stop
1
Slow down and stop, call AEr alarm
2
AEr alerts and continues running
PID current feedback disconnection detection
Example: When PID feedback is 4-20mA current signal. If the 4-5 terminal input is the source of feedback, the
inverter should slow down and stop after the feedback signal is disconnected for 10.0s during operation, and AEr
alarm should be reported, the following parameters should be set: 02-01(p.501)= 4,02-20(p.17)=
0,08-00(p.170)=X2, 08-45(P.253)=10.0s,08-46(P.254) =1.
5.9.15 PID target linear change time
Used to set the linear change time of PID target quantity
Param
eter
Name
Default
Setting range
Content
08-50
P.724
PID target linear
change time
0.00s
0~650.00s
Set the linear change time of PID target quantity
PID target linear change time
Set the time corresponding to 100% change of PID target quantity.
Setting
Setting