Appendix 1 Parameter table
APPENDIX 359
Group
Parameter
Number
Name
Setting Range
Default
Page
01-08
P.21
Acceleration/deceleration time
increments
0: Time increment is 0.01s
0
1: Time increment is 0.1s
01-09
P.20
Acceleration/deceleration
reference frequency
50Hz system setting:
1.00~650.00Hz
50.00Hz
60Hz system setting:
1.00~650.00Hz
60.00Hz
01-10
P.0
Torque boost
0.75K/1.5KF: 0~30.0%
6.0%
1.5K/2.2KF~3.7K/5.5KF: 0~30.0%
4.0%
5.5K/7.5KF~7.5K/11KF: 0~30.0%
3.0%
11K/15KF~55K/75KF: 0~30.0%
2.0%
75K/90KF and above: 0~30.0%
1.0%
01-11
P.13
Starting frequency
0~60.00Hz
0.50Hz
01-12
P.14
Load pattern selection
0: For constant torque loads (conveyor belt,etc.)
0
1: For variable torque loads (fans and pumps, etc.)
2~3: For Lifting loads
4: Multipoint V/F curve
5~13: Special two-point V/F curve
14: V/F complete detached mode
15: V/F semidetached mode
01-13
P.15
JOG frequency
0~650.00Hz
5.00Hz
01-14
P.16
JOG acceleration/deceleration
time
0~360.00s /0~3600.0s
0.50s
01-15
P.28
Output frequency filter time
0~1000ms
0ms
01-16
P.91
Frequency jump 1A
0~650.00Hz
99999
99999: Off
01-17
P.92
Frequency jump 1B
0~650.00Hz
99999
99999: Off
01-18
P.93
Frequency jump 2A
0~650.00Hz
99999
99999: Off
01-19
P.94
Frequency jump 2B
0~650.00Hz
99999
99999: Off
01-20
P.95
Frequency jump 3A
0~650.00Hz
99999
99999: Off
01-21
P.96
Frequency jump 3B
0~650.00Hz
99999
99999: Off
01-22
P.44
Second acceleration time
0~360.00s/0~3600.0s
99999
99999: Off
01-23
P.45
Second deceleration time
0~360.00s/0~3600.0s
99999
99999: Off
01-24
P.46
Second torque boost
0~30.0%
99999
99999: Off
01-25
P.47
Second base frequency
0~650.00Hz
99999
99999: Off
01-26
P.98
Middle frequency 1
0~650.00Hz
3.00Hz
Содержание SA3 Series
Страница 2: ......
Страница 420: ...Appendix 6 European Specification Compatibility Description APPENDIX 418 ...
Страница 421: ...Appendix 6 European Specification Compatibility Description Appendix 419 ...