Communication parameter group 07
PARAMETER DESCRIPTION 201
5.8 Communication parameter group 07
Group
Parameter
Number
Name
Setting Range
Default Page
07-00
P.33
COM1
Communication
protocol selection
0: Modbus protocol
1
1: Shihlin protocol
2:PLC protocol(Effective when using Shihlin built-in PLC)
07-01
P.36
COM1
inverter
communication
station number
0~254
0
07-02
P.32
COM1
Serial
communication
baud rate
0: Baud rate:4800bps
1
1: Baud rate:9600bps
2: Baud rate:19200bps
3: Baud rate:38400bps
4: Baud rate:57600bps
5: Baud rate:115200bps
07-03
P.48
COM1
data length
0: 8bit
0
1: 7bit
07-04
P.49
COM1 stop bit
length
0: 1bit
0
1: 2bit
07-05
P.50
COM1 parity check
selection
0: No parity check
0
1: Odd
2: Even
07-06
P.51
COM1 CR/LF
selection
1: CR only
1
2: Both CR and LF
07-07
P.154
COM1
Modbus
communication
format
0: 1, 7, N, 2 (Modbus, ASCII)
4
1: 1, 7, E, 1 (Modbus, ASCII)
2: 1, 7, O, 1 (Modbus, ASCII)
3: 1, 8, N, 2 (Modbus, RTU)
4: 1, 8, E, 1 (Modbus, RTU)
5: 1, 8, O, 1 (Modbus, RTU)
07-08
P.52
COM1 Number of
communication
retries
0~10
1
07-09
P.53
COM1
communication
interval allowed time
0~999.8s: Checking communication timeout with the set
value
99999
99999: No timeout check
07-10
P.153
COM1
communication
alarm action
0: Alarm and stop freely
0
1: No alarm and continuing to operation
07-11
P.34
Communication
EEPROM write-in
selection
0: When writing parameters in communication mode, write in
RAM and EEPROM
0
1: When writing parameters
through communication, only
write into RAM
07-15
P.800
CANopen slave
address
0~127
0
07-16
P.801
CANopen rate
0: 1Mbps
0
1: 500Kbps
2: 250K/280Kbps