PARAMETER DESCRIPTION 234
5.9.11 PID reverse run operation selection
PID reverse run selections is used to set whether reverse run is allowed when PID calculation result is negative.
Parameter
Name
Default Setting Range
Content
08-40
P.727
PID allowed reverse
rotation action
selection
1
0
PID does not allow reverse
1
PID allow reverse
08-41
P.728
PID in reverse
direction integral limit
0.0%
0 ~ 100.0%
It is used to set the upper limit of PID integral when run
reverse. Set to 0 when reverse run is not allowed.
08-42
P.729
PID minimum output
frequency
0.00Hz 0 ~ 10.00Hz
It is used to set the minimum PID output
PID reverse run operation selection
When PID allows reverse run, 08-41(P.728) should be set greater than 0, generally set to 100.0%. If PID does not
allow reverse run, 08-41(P.728) set 0.
08-42(P.729) is used to set the lowest output frequency in PID calculation. If output is less than 08-42(P.729) ,
inverter stops output.
5.9.12 Pressure unit (Bar) setting
Used by setting the maximum value of PID target value.
Param
eter
Name
Default
Setting range
Content
08-43
P.251
PID pressure
range
(Bar) setting
100.0
1.0~100.0
Set the maximum value of PID target value.
Pressure unit (Bar) setting
Example: if the pressure sensor feedback range is 0~10V and the corresponding pressure range is 0~16.0 bar,
then set 08-43(P.251) to 16.0.
5.9.13 PID unit selection
The unit of PID pressure displayed when used with PU301C.
Parameter
Name
Default
Setting range
Content
08-44
P.252
PID unit selection
0
0
%
1
bar
2
--
3
kgs
4
kg
5
psi
6
Pa
7
kPa
8
MPa
9
C
PID unit selection
Example: If the pressure unit displayed by PU301C is bar, then 08-44(P.252) is set as 1.
Setting
Setting
Setting