Appendix 1 Parameter table
APPENDIX 365
Group
Parameter
Number
Name
Setting Range
Default
Page
02-44
P.543
Terminal FM output function
selection
8: Excitation current, use motor rated current as
100%. (Valid only when 00-21(P.300) or 00-22 (P.370)
is set to 3~6)
0
9: Output torque, use two times motor rated torque as
100%.(Valid only when 00-21 (P.300) or 00-22 (P.370)
is set to 3~6)
10: Output power, use two times motor rated power as
100%.
11: High-speed pulse input, use 100KHz as 100%.
12: Motor speed, use 02-51 (P.55) as 100%
02-45
P.64
Terminal AM1 output signal
selection
0: Output 0~10V across terminal AM1-5.
0
02-45
P.64
Terminal AM1 output signal
selection
1: Reserved
0
2: Output 0~20mA across AM1-5.
3: Output 4~20mA across AM1-5.
02-46
P.191
Terminal AM1 output gain
0~5000
3210
02-47
P.190
Terminal AM1 output bias
0~5000
80
02-48
P.538
Terminal AM2 output signal
selection
Same as 02-45
0
02-49
P.536
Terminal AM2 output gain
0~5000
3210
02-50
P.535
Terminal AM2 output bias
0~5000
80
02-51
P.55
Maximum analog output
frequency reference
50Hz system: 1.00~650.00Hz
50.00Hz
60Hz system: 1.00~650.00Hz
60.00Hz
02-52
P.56
Maximum analog output
current reference
0~500.00A: below Frame G
Accordin
g to
frame
0~5000.0A: Frame G and above
02-53
P.539
Terminal AM2 fixed output
level
0~100.0%
0.0%
02-54
P.541
Terminal AM1/FM fixed
output level
0~100.0%
0.0%
02-55
P.592
PT100 thermistor voltage
level 1
0~10.00V
5.00V
02-56
P.593
PT100 thermistor voltage
level 2
0~10.00V
7.00V
02-57
P.594
PT100 thermistor level 1
frequency
0~650.00Hz
0.00Hz
02-58
P.595
PT100 thermistor level 1
delay time
0~6000s
60s
02-59
P.187
FM calibration coefficient
0~9998
450