Analog input and output parameter group 02
PARAMETER DESCRIPTION 135
5.3.10 Terminal FM analog output function selection
Selects monitor item output by terminal FM, when terminal
HDO output function is FM.
Parameter
Name
Default Setting Range
Content
02-44
P.543
Terminal FM output
function selection
0
0
Output frequency, use 02-51 (P.55) value as 100%.
1
Output current, use 02-52 (P.56) value as 100%.
2
Output DC bus voltage, use the
OV trigger voltage as 100%.
3
Output inverter temperature accumulate rising rate, use NTC
trigger level as 100%.
4
Output inverter thermal relay accumulate rate, use the digital
thermal relay trigger level ( 06-00 ( P.9 ) ≠ 0 ) or the thermal
relay on IGBT trigger level ( 06-00 (P.9) = 0) as 100%.
5
Target frequency, use 02-51(P.55) value as 100%.
6
Fixed output, voltage or current output level can be set by
02-54 (P.541)
7
Output voltage, use inverter rated voltage as 100%
8
Excitation current, use motor rated current as 100%. (Valid
only when 00-21(P.300) or 00-22 (P.370) is set to 3~6)
9
Output torque, use two times motor rated torque as
100%.(Valid only when 00-21 (P.300) or 00-22 (P.370) is set
to 3~6)
10
Output power, use two times motor rated power as 100%.
11
High-speed pulse input, use 100KHz as 100%.
12
Motor speed, use 02-51 (P.55) as 100%
Usage of analog output terminal FM
To calibrate terminal FM, please refer to 5.3.16 FM calibration parameter.
5.3.11 Terminal AM1 signal selection and processing
Adjust terminal AM1 analog output type and level.
Parameter
Name
Default Setting Range
Content
02-45
P.64
Terminal AM1 output
signal selection
0
0
Output 0~10V across terminal AM1-5.
1
Reserved
2
Output 0~20mA across AM1-5.
3
Output 4~20mA across AM1-5.
02-46
P.191
Terminal AM1 output
gain
3210
0~5000
---
02-47
P.190
Terminal AM1 output
bias
80
0~5000
---
Terminal AM1 signal selection and processing
Terminal AM1 output current/voltage is set by toggle switch SW3 on the control board with parameter 02-45(P.64).
When selecting the output type of AM1 terminal, first dial toggle switch SW3 to correspond position, then set 02-45
(P.64)value.