5.3.3 Proportional linkage gain
This function is used to multiply frequency command from external analog input terminal.
When multiple inverters are
running in proportion, it is effective to use this function to fine-tune the frequency command from master inverter to
slave inverter.
Parameter
Name
Default Setting Range
Content
02-06
P.185
Proportional
linkage
gain
0%
0~100%
---
Proportional linkage gain
When output frequency is lower than 01-01(P.2), it is equal to lower limit frequency 01-01(P.2).
When output frequency is higher than 01-00(P.1), it is equal to upper limit frequency 01-00(P.1).
After multiplying the setting frequency by 02-06(P.185) value, add and subtract can be performed as follows:
For example: When the set frequency is 50Hz, 02-06(P.185)=50% and the external analog input signal is 0~10V.
25Hz
0V
5V
10V
50Hz
75Hz
100Hz
The target frequency
Given by the voltage
of terminal 2-5
02-06
(
P.185
)
=100%
02-06
(
P.185
)
=50%
In the above figure,when 0V is given, the target frequency is 50Hz - (50Hz × 50%) = 25Hz;
when 5V is given, the target frequency is 50Hz - (50Hz × 0%) = 50Hz;
when 10V is given, the target frequency is 50Hz + (50Hz × 50%) = 75Hz.
Note: 1. For proportional linkage signal input, please refer to the description of parameter 02-07 (P.240).
2. When use terminal 4-5 analog (voltage/current) signal as proportional linkage signal input terminal, please
refer to parameter 02-20(P.17); for the setting of external analog signal frequency range, please refer to
parameter 02-09(P.38), 02-21(P.39), 02-30(P.508), 02-20(P.17), 02-08(P.73), 02-29(P.531).