Appendix 1 Parameter table
APPENDIX 380
Group
Parameter
Number
Name
Setting Range
Default Page
07-33
P.818
PU Number of
communication
retries
0~10
1
07-34
P.819
PU communication
interval allowed
time
0~999.8s: Check communication timeout with the set value
99999
99999: Off
07-35
P.820
PU communication
error handling
0: Alarm and stop freely.
1
1: No alarm and continue running
07-41
P.826
Expansion
communication
card number of
communication
retries
0~10
1
07-42
P.827
Expansion
communication
card
communication
error handling
0: Alarm and idling and stopping
1
1: No alarm and continue running
07-43
P.828
Expansion
communication
card
communication
interval allowed
time
0~999.8s: Check communication timeout with the set value
99999
99999: Off
07-44
P.829
Version of EP301
communication
card
Read only
read
221
07-45
P.830
IP configuration
0: Static IP
0
222
1: Dynamic IP
07-46
P.831
IP address 1
0~255
192
222
07-47
P.832
IP address 2
0~255
168
222
07-48
P.833
IP address 3
0~255
2
222
07-49
P.834
IP address 4
0~255
102
222
07-50
P.835
Subnet mask 1
0~255
255
222
07-51
P.836
Subnet mask 2
0~255
255
222
07-52
P.837
Subnet mask 3
0~255
255
222
07-53
P.838
Subnet mask 4
0~255
0
222
07-54
P.839
Default gateway 1
0~255
192
222
07-55
P.840
Default gateway 2
0~255
168
222
07-56
P.841
Default gateway 3
0~255
2
222
07-57
P.842
Default gateway 4
0~255
100
222
08-00
P.170
PID function
selection
0: Off
0
0X: Parameter 08-03(P.225) as target value.
1X: Terminal 2-5 input as target source
2X: Terminal 4-5 input as target source
3X: Terminal 3-5 input as target source
4X: Terminal HDI input as target source
X1: Terminal 2-5 input as feedback source
X2: Terminal 4-5 input as feedback source
X3: Terminal 3-5 input as feedback source
Содержание SA3 Series
Страница 2: ......
Страница 420: ...Appendix 6 European Specification Compatibility Description APPENDIX 418 ...
Страница 421: ...Appendix 6 European Specification Compatibility Description Appendix 419 ...