PID parameter group 08
PARAMETER DESCRIPTION 225
5.9.1 PID function selection
Inverter can control flow, volume or pressure by PID control. By using analog signal or parameter setting as target
source, and with analog signal as feedback source, it form a closed loop control system.
Parameter
Name
Default Setting Range
Content
08-00
P.170
PID function selection
0
0
Off
0X
Parameter 08-03(P.225) as target value.
1X
Terminal 2-5 input as target source
2X
Terminal 4-5 input as target source
3X
Terminal 3-5 input as target source
4X
Terminal HDI input as target source
X1
Terminal 2-5 input as feedback source
X2
Terminal 4-5 input as feedback source
X3
Terminal 3-5 input as feedback source
08-01
P.171
PID feedback control
method
0
0
Negative feedback control.
1
Positive feedback control.
PID function selection
During PID control, frequency displayed on screen is inverter output frequency.
For terminal 2-5, terminal 3-5 and terminal 4-5 input signal filtering please refer to parameters 02-10(P.60)
02-22(P.528) 02-31(P.527).
Note:
When setting target source and feedback source, please pay attention to 08-00(P.170) and
02-00
(P.500)
~02-02(P.504) setting, terminal priority : 2-5 > 4-5 >3-5.
Setting