Application parameter group 10
PARAMETER DESCRIPTION 267
Parameter
Name
Default Setting Range
Content
10-46
P.268
Regeneration avoid
action voltage level
380V
155~400V
220V models
760V
310~800V
440V models
10-47
P.269
Regeneration avoid
function DC bus
voltage detection
sensitivity at
deceleration
0
0
Prevent regeneration avoidance from failing according to
bus voltage change rate
1~5
Set the sensitivity to detect the bus voltage change rate.
Larger number, higher sensitivity.
10-48
P.270
Regeneration avoid
frequency
compensation value
6.00Hz
0~10.00Hz
Set the limit value of regenerative avoid frequency
compensation.
99999
Off.
10-49
P.271
Regeneration avoid
voltage gain coefficient
100.0%
0~400.0%/0~
40.0%
Setting range is related to 10-45 (P.267). If 10-45
(P.267) >10, the setting range is 0~40.00%; If 0-45 (P.267)
<10, the setting range is 0-400.0%.
Adjust the response speed during regeneration avoid
operation. Increasing the set value will improve the response
to the bus voltage changes, but output frequency may be
unstable. If cannot reduced vibration even if 10-49 (P.271) is
reduced, please reduce 10-50 (P.272).
10-50
P.272
Regeneration avoid
frequency gain
coefficient
100.0%
0~400.0%/0~
40.0%
Regeneration avoid function
Regeneration avoid function: In case too many regeneration energy in DC bus trigger inverter OV alarm.
Regeneration avoid function will reduce bus voltage by increasing inverter output frequency when regeneration
voltage exceeds the level, thus avoiding inverter from reporting OV alarm (as shown in the following diagram).
5.11.15 Over excitation deceleration function
Over excitation deceleration function increases the energy consumption of motor by increasing the magnetic flux at
deceleration and stop, which can shorten the deceleration time without braking resistor.
Parameter
Name
Default Setting Range
Content
10-51
P.264
Over excitation
deceleration
0
0
Off.
1
Over excitation deceleration is on.
10-52
P.265
Over excitation current
level
150.0%
0~200.0%
When output current is above the setting level in over
excitation deceleration, over excitation gain will decrease
automatically.
10-53
P.266
Over excitation gain
1.10
1.00~1.40
---
Setting