Fronius Symo Advanced - Installa-
tion
10.0-3 208-240
12.0-3 208-240
15.0-3 480
20.0-3 480
22.7-3 480
24.0-3 480

EN-US

Installation instructions

Grid-connected inverter

42,0426,0296,EA 016-17062021

Содержание 10.0-3 208-240

Страница 1: ...fied sustainable forests FSC Perfect Charging Perfect Welding Solar Energy Fronius Symo Advanced Installa tion 10 0 3 208 240 12 0 3 208 240 15 0 3 480 20 0 3 480 22 7 3 480 24 0 3 480 EN US Installat...

Страница 2: ......

Страница 3: ...r deform the mounting bracket 17 Knockouts 18 Safety 18 General 18 Knocking or Drilling Out Knockouts 19 AC 21 Suitable Grids 23 Connecting the inverter to the public grid AC side 24 Safety 24 Permitt...

Страница 4: ...pdating Inverter Software 57 USB Flash Drive as a Data Logger 57 Data on the USB thumb drive 57 Data Amount and Memory Capacity 58 Buffer Memory 58 Suitable USB Thumb Drives 59 USB Stick for Updating...

Страница 5: ...the installation site For installations in Canada the installations must be done in accordance with applicable Canadian standards Rapid shutdown The rapid shutdown RSD can be triggered via loss of th...

Страница 6: ...sponsibility of the installer to ensure that the completed PV system meets the rapid shutdown functional requirements This equipment must be installed according to the manufacturer s installation inst...

Страница 7: ...ctions Safety WARNING Danger from incorrect operation and work that is not carried out properly This can result in severe personal injury and damage to property Only qualified staff are authorized to...

Страница 8: ...a parallel arc Notice Before an inverter can be reset following a detected electric arc check the entire affected photovoltaic system for any damage The manufacturer s specifications for connection in...

Страница 9: ...m 8202 9842 ft 2500 3000 m 6561 8202 ft 2000 2500 m 9842 11154 ft 3000 3400 m 950 V 900 V 850 V UDC max ft m 15 0 3 24 0 3 480 11154 ft 3400 m IMPORTANT The inverter must not be installed or operated...

Страница 10: ...accumulation e g iron filings as this can cause damage to the inverter Do not install the inverter in Greenhouses Storage or processing areas for fruit vegetables or viticulture products Areas used i...

Страница 11: ...r the inverter 4 in 100 mm 4 in 100 mm 8 in 200 mm 40 F 140 F 40 C 60 C 0 100 Only install on a solid non flammable surface Max ambient temperatures 40 F 140 F 40 C 60 C Relative humidity 0 100 The ai...

Страница 12: ...verter is equipped with a Power Line Communication PLC transmitter on the DC side Its function is to ensure rapid shutdown in accordance with US safety standard NEC 2017 Art 690 12 The PLC is implemen...

Страница 13: ...Preparation 13...

Страница 14: ...14...

Страница 15: ...y ensured when the inverter is mounted and firmly screwed into the mounting bracket The mounting bracket without inverter and ventilation channel has no NEMA protection Selecting Dowels and Screws Imp...

Страница 16: ...ON OFF Lock 1 2 3 lb 4 Installing the Mounting Bracket on a Wall The mounting bracket must be secured in at least four places NO NEMA ENCLOSURE TYPE 1 2 16...

Страница 17: ...metal carrier The mounting bracket must be secured in at least four places 1 Do not warp or deform the mounting bracket Notice When attaching the mounting bracket to the wall or to a column make sure...

Страница 18: ...rating outdoors NOTE When installing outdoors only use waterproof conduit fittings and conduits Conduit fittings and conduits are not part of the scope of supply for the inverter General 1 1 4 in 1 1...

Страница 19: ...kouts required for the available cables Use suitable eye protection when knocking drilling out the knock outs Only knock out knockouts using a hammer or screwdriver from the inside outwards Only use s...

Страница 20: ...1 2 20...

Страница 21: ...AC 21...

Страница 22: ...22...

Страница 23: ...208 V 220 V 220 V 50 Hz 208 240 V 208 V 480 V 440 V 50 Hz 415 V Microgrid 208 V Microgrid 50 Hz 208 240 V Microgrid 50 Hz 480 V Microgrid 480 V 480 V 480 V Appropriate inverter Symo Advanced 10 0 3 20...

Страница 24: ...components can cause serious injury and damage to property An electric shock can be fatal All electrical connections must be made in accordance with the national standard e g for the US National Elect...

Страница 25: ...conductor must have a current carrying capacity of at least 1 A Permitted cables AC cables with the following design can be connected to the AC terminals of the inverter Cu Al Cu Copper Cu or aluminu...

Страница 26: ...2 14 12 2 14 14 2 14 16 2 14 10 2 14 12 2 14 14 2 14 16 2 16 5 16 5 16 14 2 16 16 2 16 10 5 16 12 2 16 14 2 16 16 2 1 tested and inspected as per UL 2 not inspected as per UL connection possible 3 wit...

Страница 27: ...r sandpaper aluminum particles may get stuck and can transfer to other cables 2 After removing the oxide layer of the cable end rub in a neutral grease e g acid free and alkali free Vaseline 3 Then im...

Страница 28: ...ain switch connection block the cables may be damaged when the inverter is pivoted or the inverter may not be able to be pivoted IMPORTANT Do not lay AC cables over the shaft of the DC main switch or...

Страница 29: ...10 0 3 208 240 3 N 10 000 W C 80 A Fronius Symo Advanced 12 0 3 208 240 3 N 12 000 W C 80 A Fronius Symo Advanced 15 0 3 480 3 N 15 000 W C 80 A Fronius Symo Advanced 20 0 3 480 3 N 20 000 W C 80 A F...

Страница 30: ...r the residual current cir cuit breaker type A in individual cases and depending on local conditions For this reason Fronius recommends that you use a residual current circuit breaker suitable for fre...

Страница 31: ...DC 31...

Страница 32: ...32...

Страница 33: ...onents can cause serious injury and damage to property An electric shock can be fatal All electrical connections must be made in accordance with the national standard e g for the US National Electrica...

Страница 34: ...4X before operating outdoors NOTE When connecting aluminum cables follow all national and international guidelines regarding the connection of aluminum cables follow the instructions of the cable manu...

Страница 35: ...aulty fuses This can result in fire Only replace faulty fuses with new ones of the same rating The inverter is delivered with metal bolts as standard Option DC SPD DC 2 1 DC 1 1 DC 1 3 DC 1 2 DC 2 3 D...

Страница 36: ...combinations can be used for wiring Select a sufficiently large cable cross section based on the actual device output AWG roun d AWG stran ded AWG stranded round AWG round round AWG stranded stranded...

Страница 37: ...3 12 0 3 208 240 0 to 11 154 ft 0 to 3400 m 600 V Symo Advanced 15 0 3 24 0 3 480 0 to 6561 ft 0 to 2000 m 1000 V 653 1 to 8202 ft 200 0 to 2500 m 950 V 820 2 to 9842 ft 250 0 to 3000 m 900 V 984 2 t...

Страница 38: ...Connection Requirements 1 Carefully clean off the oxide layer of the stripped end of the cable e g using a knife IMPORTANT Do not use brushes files or sandpaper aluminum particles may get stuck and c...

Страница 39: ...42 0201 4480 10 0 3 12 0 3 208 240 max 41 5 A 15 0 3 20 0 3 22 7 3 24 0 3 480 max 51 A 12x 1 8 Nm 16 lbf in B A S I C M P P T R A C K E R 2 O F F 3 Torque Nm lbf in see printing near wire terminal 4 5...

Страница 40: ...across the DC main switch connection block the cables may be damaged when the inverter is pivoted or the inverter may not be able to be pivoted IMPORTANT Do not lay DC cables over the shaft of the DC...

Страница 41: ...Laying Solar Net Cables 41...

Страница 42: ...42...

Страница 43: ...Data communication Lay data commu nication cables 1 2 3 4 5 22 lbf in 2 5 Nm 6 43 EN US...

Страница 44: ...n the Inverter WARNING Danger of residual voltage from capacitors An electric shock can be fatal Wait until the capacitors have discharged Discharge takes 5 minutes WARNING An inadequate ground conduc...

Страница 45: ...1 2 1 3 TX20 10 6 lbf in 1 2 Nm 1 2 4 5 45 EN US...

Страница 46: ...46...

Страница 47: ...Finally 47...

Страница 48: ...48...

Страница 49: ...on and condensation in the conduits seal all conduits in use with a perman ently elastic sealant seal every incoming and outgoing conduit seal both conduit ends Conduit Conduit AC Inside Outside DC 4...

Страница 50: ...ivot the inverter in the mounting bracket when the DC main switch is off Do not use excessive force to clip on the inverter and pivot it The fixing screws in the data communication area of the inverte...

Страница 51: ...4 3 in 1 ON OFF Lock 22 1 lbf in 2 5 Nm 2 3 4 51 EN US...

Страница 52: ...22 1 lbf in 2 5 Nm 5 6 AC ON 2 ON OFF Lock 1 7 52...

Страница 53: ...al support 1 2 1 S e l e c t C o u n t r y 1 2 5 0 H z I n t e r n a t i o n a l 5 0 H z 2 Country setup examples The available country setups may change during a software update Therefore the followi...

Страница 54: ...C O N F I G L o a d i n g C o u n t r y S e t u p 3 6x 7x 1 2 4 4x 5x 1 2 5 S E T U P A u t o D a y l i g h t s a v i n g 1 2 6 B A S I C M P P T R A C K E R 2 1 2 7 8 9 54...

Страница 55: ...Options 55...

Страница 56: ...56...

Страница 57: ...ly Only delete all files together sys fld csv DALO fld log file Log file for reading out data in Fronius Solar access You can find additional information on the Fronius Solar access software in the DA...

Страница 58: ...e If the logging interval is set longer this time frame is extended accordingly FLD file The FLD file should not be larger than 16 MB At a logging interval of 5 minutes this cor responds to a storage...

Страница 59: ...dustrial USB thumb drives look for the USB IF logo The inverter supports USB thumb drives using the following file systems FAT12 FAT16 FAT32 Fronius recommends that the USB thumb drive only be used fo...

Страница 60: ...ng a USB stick IMPORTANT To prevent a loss of data the connected USB stick should only be removed under the following conditions via the SETUP and Safely remove USB hardware menu items when the Data T...

Страница 61: ...fect on the inverter by installing an elec trical device in this area Caution should be taken when installing a device that may output significant amounts of heat or radio interference Always ensure t...

Страница 62: ...62...

Страница 63: ...Care and maintenance 63...

Страница 64: ...64...

Страница 65: ...l check to ensure that all screw connections are tightly fastened Maintenance and service work may only be carried out by Fronius trained service techni cians Cleaning Wipe the inverter if necessary w...

Страница 66: ...66...

Страница 67: ...67 EN US...

Страница 68: ...INTERNATIONAL GMBH Froniusstra e 1 A 4643 Pettenbach AUSTRIA contact fronius com www fronius com Under www fronius com contact you will find the addresses of all Fronius Sales Service Partners and lo...