Application parameter group 10
PARAMETER DESCRIPTION 266
Frequency acceleration time of V/F complete separation indicates the time accelerates from 0 to base frequency
(01-06(P.7)).Frequency deceleration time indicates the time decelerates from base frequency to 0 (01-07(P.8));
voltage acceleration time of VF complete separation indicates the time accelerates from 0 to the rated motor
voltage t1 (10-42(P.702)). Voltage deceleration time of VF complete separation indicates the time decelerates from
the rated motor voltage to 0 t2 (10-43(P.703)).
Time t
Output
frequency
Hz
Base frequency
Set frequency
Actual frequency
acceleration time
Set frequency
acceleration time
Actual frequency
deceleration time
Set frequency
deceleration time
T1
T2
Time t
Output
voltage
V
Rated motor voltage
Target voltage
Actual voltage
acceleration time
Set voltage
acceleration time
Actual voltage
deceleration time
Set voltage
deceleration time
t1
t2
Use 10-41(P.701) to set digital voltage, the setting value cannot exceed motor rated voltage.
When voltage acceleration time is less than frequency acceleration time or voltage deceleration time is more than
frequency deceleration time, voltage stall or current stall may occur during acceleration/ deceleration, which leads
to alarm. So it is suggested that 10-42(P.702)> 01-06(P.7) and 10-43(P.703) < 01-07
(P.8)
.
5.11.14 Regeneration avoid function
When inverter load inertia is larger, during deceleration or other process PN voltage will increase due to regenerative
power, and OV alarm will occur. This function can keep PN voltage fixed and prevent PN level from increasing to
OV level by adjusting inverter output frequency and voltage.
Parameter
Name
Default Setting Range
Content
10-45
P.267
Regeneration avoid
function selection
0
0
Off.
1
Regeneration avoid function is always on. (Automatic
calculate Acc/Dec speed )
2
Regeneration avoid function is on only during constant
speed operation (Automatic calculate Acc/Dec speed )
11
Regeneration avoid function is always on. (Manual mode,
Acc/Dec speed is set by 10-49(P.271) and 10-50(P.272))
12
Regeneration avoid function is on only during constant
speed operation (Manual mode, Acc/Dec speed is set by
10-49(P.271) and 10-50(P.272))