- 86 -
7-2
Function Code List - Basic Operation Function
Code
No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
User
Setting
Value
1007
Upper frequency limit
5-599Hz
0.01Hz
60
1008
Lower frequency limit
0.05-200Hz
0.01Hz
0.05
1009
Carrier frequency adjustment
0-130
1
※
1
1010
Acceleration/deceleration curve
1: Linear
2: S-shaped
3: Reduction of acceleration/deceleration
1
1
1011
Reference frequency for
acceleration/deceleration
1-120Hz
0.01Hz
※
1
1012
1st acceleration time
0-6,500 sec.
0.1 s
※
2
-
1
1013
2nd acceleration time
0-6,500 sec.
0.1 s
※
2
-
2
1014
3rd acceleration time
0-6,500 sec.
0.1 s
※
2
-
3
1015
4th acceleration time
0-6,500 sec.
0.1 s
※
2
-
4
1016
1st deceleration time
0-6,500 sec.
0.1 s
※
2
-
5
1017
2nd deceleration time
0-6,500 sec.
0.1 s
※
2
-
6
1018
3rd deceleration time
0-6,500 sec.
0.1 s
※
2
-
7
1019
4th deceleration time
0-6,500 sec.
0.1 s
※
2
-
8
1020
JOG acceleration/deceleration time
0-20 sec.
0.1 s
0.1
1021
JOG frequency
0-60Hz
0.01Hz
5
1022
1st Start of S-shaped acceleration
0-200%
1%
50
1023
1st End of S-shaped acceleration
0-200%
1%
50
1024
Gradient of middle of 1st S-shaped
Acceleration
0-100%
1%
0
1025
1st Start of S-shaped deceleration
0-200%
1%
50
1026
1st End of S-shaped deceleration
0-200%
1%
50
1027
Gradient of middle of 1st S-shaped
Deceleration
0-100%
1%
0
1028
2nd Start of S-shaped acceleration
0-200%
1%
50
1029
2nd End of S-shaped acceleration
0-200%
1%
50
1030
Gradient of middle of 2nd S-shaped
Acceleration
0-100%
1%
0
1031
2nd Start of S-shaped deceleration
0-200%
1%
50
1032
2nd End of S-shaped deceleration
0-200%
1%
50
1033
Gradient of middle of 2nd S-shaped
Deceleration
0-100%
1%
0
1034
1035
1036
1st speed frequency selection A
1st speed frequency selection B
1st speed frequency selection C
1: Operation panel
2: External analog VIF1 voltage (0
-
5V)
3: External analog VIF1 voltage
(0
-
10V or potentiometer)
4: External analog VIF2 voltage (0
-
5V)
5: External analog VIF2 voltage
(0
-
10V or potentiometer)
6: External analog VIF3 voltage (0
-
5V)
7: External analog VIF3 voltage
(0
-
10V or potentiometer)
8: External analog VIF1 current (4
-
20mA)
9: External analog VIF2 current (4
-
20mA)
10: External analog VIF3 current (4
-
20mA)
21: Terminal block stepping
22: Communication
25:Pulse train input
26:External analog VIF1 forward / reverse run
operation (0
-
10V, 5V reference)
27:External analog VIF2 forward / reverse run
operation (0
-
10V, 5V reference)
28:External analog VIF3 forward / reverse run
operation (0
-
10V, 5V reference)
29: Pulse train input (subPG
:
option)
1
1
1
1
1037
Terminal board step set
0.1-10Hz/sec
0.1Hz/sec
2.5
1038
Keep or clear frequency
0: Keep the frequency
1: Reset frequency after power off
2: Reset frequency after stop
1
0
1101
Operation command selection
1: Operation panel
2: External terminal
3: Communication
4: External terminal (3wired operation)
1
1
1102
Starting method
1: Starting frequency
2: Flying start
3: Starting frequency after DC braking
1
1
1103
Starting frequency
0.05-60Hz
0.01Hz
1
1104
Operation start frequency
0-20Hz
0.01Hz
0
1105
Start delay time
0-5 sec.
0.1 s
0
1106
Start standby time
0-120 sec.
0.1 s
0
1107
Start standby frequency
0.05-60Hz
0.01Hz
5