- 120 -
7-3
Description of Functions
F1037
Terminal board step set
This function set the variation of the frequency when terminal board stepping function is used.
Code No.
Function Name
Data Content
Setting Resolution
Factory Presets
F1037
Terminal board step
set
0.1-10Hz/sec
0.1Hz/sec
2.5
●
For a second after AD2 or AD3 was shorted, the set frequency increases or decreases at a 0.05Hz/sec.
After one
second progress, the frequency increases or decreases at a selected pace on F1037.
●
Regarding the terminal block stepping function, please refer to F1002:1st speed frequency setting selection.
F1038
Keep or clear frequency
This function set the condition to clear the set frequency when the terminal board step frequency function is used.
Code No.
Function Name
Data Content
Setting Resolution
Factory Presets
F1038
Keep or clear frequency
0: Keep the frequency
1: Reset frequency after power off
2: Reset frequency after stop
1
0
●
In the case of F1308 = 0, the set frequency is kept.
●
In the case of F1308 = 1, the set frequency can be cleared when the inverter turned power off.
●
In the case of F1308 = 2, the set frequency can be cleared when the inverter stopped.
●
The set frequency to clear is the frequency selected by multi-speed drive.
Example 1) In the case of 3rd speed is selected, F2103
=
3rd speed frequency is cleared.
●
Except for terminal board step function, if F1038 is set 1 or 2, the set frequency is not cleared
Example 2) In the case of F1001 = 1 (1st speed frequency = operation panel), if F1038 is set "2", the set frequency is
not cleared when the inverter stopped.
●
If you want to clear the set frequency anytime, Please use T-FCL signal.
When the terminal board step function is
used, the setup frequency is cleared to "0" if T-FCL signal is turned on,
Except for terminal board step function, the
set frequency is not cleared if T-FCL signal is turned on.
Starting • braking function
F1101
Operation command selection
A function for selecting whether the operation/stop command of inverter is sent through operation panel or through
external signals.
Code No.
Function Name
Data Content
Setting Resolution
Factory Presets
F1101
Operation command
selection
1: Operation panel
2: External terminal
3: Communication
4: External terminal (3 wired operation)
1
1
●
When F1101=1 (operation panel), Drive key and Stop key on the operation panel are active. User push the Drive key,
the inverter will start, and push the Stop key, the inverter will stop. If RREV is ON, then the inverter will drive to
reverse revolution from revolution direction command.