- 133 -
C
h
ap
ter
7
7-3
Description of Functions
LED display function
F1201
Monitor display selection
A function for switching the display contents of operation panel.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1201
Monitor display selection
1: Frequency [Hz]
2: Output current [A]
3: Speed [rpm]
4: Load factor [%]
5: No unit display
1
1
●
The change of the display value and display method in stopped state, standby state as well as operating state is
shown in the following table.
F1201
Stopped
Standby/Operating
1
Flashing setting frequency
Normally-on output frequency
2
Flashing 0 [A]
Normally-on output current
3
Flashing speed (*1)
Normally-on speed (*1)
4
Flashing 0 [%]
Normally-on load factor
5
The output monitor can be changed using F1202.
(*1)The display contents may vary depending the motor control mode. The display contents are as shown in the table below.
Motor control mode
In operation (operating)
Stopped
Sensorless vector control
Estimated speed of motor
0
Others
(V/f·vector)
Detecting speed of PG sensor
Detecting speed of PG sensor
Note: By using F1603, this code can be set even when the operation function is locked.