- 42 -
4-5
Composition of Control Circuit Terminals
4-5-7
Connection of PG Sensor
1) Connection example when the control terminal of main control board is used (open-collector mode)
*1:
Set function code F8109 (PG:PG output formation selection) to 1.
*2:
Both phase A pulse and phase B pulse can be input.
*3:
Please use as shown in the example above when the power supply of PG sensor is 24V. And, as shown in the
connection diagram, using the inverter to provide 24V power supply eliminates the need for an external power
supply.
2)
Connection example when the control terminal of main control board is used (push-pull mode)
*1: When the power supply of PG sensor is 24V, the inverter can be used for supplying 24V power to the
user.
Phase B
pulse
Phase A
pulse
Inverter
The power supply of PG
sensor can be supplied
by inverter
Phase A
pulse
Phase B
pulse
Inverter