- 76 -
6-2
Test Run
(2) Confirmation items during test run
Please confirm the contents listed in the table below
Table 6-11 Confirmation items during test run
Item
Result
1
Motor rotation direction
Is it the specified rotation direction?
2
Motor operation 1
Are the acceleration and deceleration smooth?
3
Motor operation 2
Is there any abnormal sound or vibration?
4
Inverter fan operation
Is the fan running?
5
Inverter display and others
Are the display on operation panel and equipment normal?
※
In the factory default configuration, fans of the inverter performs the ON/OFF control automatically by the fin temperature
of the inverter. The trial operation, set to (F1318 = 1) ON always control the fan, please check the operation of the fan.
*When it is confirmed that there is no problem, please increase the set frequency before operation. Similarly, for the
operation with increased frequency, the above confirmation items shall also be checked.
Содержание SVCO6
Страница 1: ...High Performance Vector Control Inverter Instruction Manual SANKEN ELECTRIC CO LTD ...
Страница 2: ......
Страница 324: ... 322 Memorandum ...
Страница 325: ......