- 287 -
-
287
-
C
h
ap
ter
7
7-4
Serial Communication Function
■
Write in register address (at F4103=0: the time of register number A)
Process
method
Register No.
Description
DEC
HEX
Write in
1000
3E8H
Frequency
command
Setting of target frequency (1st speed)
1001
3E9H
Operation command
BIT 0
Not used
BIT 1
Forward run
1=Enabled
0=Disabled
BIT 2
Reverse run
1=Enabled
0=Disabled
BIT 3
Stop
1=Enabled
0=Disabled
BIT4 and above
Not used
1002
3EAH
Rest command
BIT 0
Alarm reset
1=Enabled
0=Disabled
BIT1 and above
Not used
1003-1009
3EBH-3F1H
System reserved
■
Write in register address (at F4103=1: the time of register number B)
Process
method
Register No.
Description
DEC
HEX
Write in
9500
251CH
Frequency
command
Setting of target frequency (1st speed)
9501
251DH
Operation command
BIT 0
Not used
BIT 1
Forward run
1=Enabled
0=Disabled
BIT 2
Reverse run
1=Enabled
0=Disabled
BIT 3
Stop
1=Enabled
0=Disabled
BIT4 and above
Not used
9502
251EH
Rest command
BIT 0
Alarm reset
1=Enabled
0=Disabled
BIT1 and above
Not used
9503-9509
251FH-2525H
System reserved
3
)
Batch operation
By setting the address (inverter number) to 0, batch operation shown in the following table can be carried out.
·
IN=0 (broadcast mode)
·
During batch operation, the inverter returns no response.
■
Batch operation register address (at F4103=0: the time of register number A)
Process method
Register No.
Description
DEC
HEX
Batch operation
3000
BB8H
Selecting inverters for batch operation
3001-3002
BB9H-BBAH
Specifying direction of rotation for inverters in batch control
3001
Selecting inverters for batch control
3002
Direction of rotation
1=Forward, 2=Reverse
3003
BBBH
Releasing inverters in batch operation
3004
BBCH
Batch start
1=Start
3005
BBDH
Batch stop
1=Stop
3006-3009
BBEH-BC1H
System reserved
■
Batch operation register address (at F4103=1: the time of register number B)
Process method
Register No.
Description
DEC
HEX
Batch operation
9700
25E4H
Selecting inverters for batch operation
9701-9702
25E5
H-
25E6
H
Specifying direction of rotation for inverters in batch control
9701
Selecting inverters for batch control
9702
Direction of rotation
1=Forward, 2=Reverse
9703
25E7
H
Releasing inverters in batch operation
9704
25E8
H
Batch start
1=Start
9705
25E9
H
Batch stop
1=Stop
9706-9709
25EA
H-
25ED
H
System reserved