7-4 Serial Communication Function
■
Reading register address (at F4103=1: the time of register number B)
Processing
method
Register No.
Description
DEC
HEX
Reading
9600
2580H
Alarm content
0 = No alarm; Other = list of alarm codes
※
1
9601
2581H
Reading of command frequency
9602
2582H
Reading of output frequency
9603
2583H
Reading of output current
9604
2584H
Reading of DC voltage
9605
2585H
Reading of radiator temperature
9606
2586H
Reading of load factor
9607
2587H
Reading of Operation Status 1
BIT0-BIT4
JOG
+
16th speed operation (operation status)
0000
:
speed segment 0, JOG operation
00001
:
1st speed operation
00010
:
2nd speed operation
…..…..…..…..…..
10000
:
16th speed operation
BIT5
Operation by external analog input frequency
(operation status)
BIT6
Operation by option input frequency
(operation status)
BIT7
1 = warning; 0 = no warning
BIT8
1 = alarm; 0 = no alarm
BIT9 and above
System reserved
9608-9609
2588H-2589H
Reading of Operation Status 2
BIT0-BIT13
STATUS FLAG(32bit)
※
2
BIT14 and above
System reserved
9610
258AH
Reading of Operation Status 3
System reserved
9611
258BH
Reading of Operation Status 4
System reserved
9612
258CH
Reading of external terminal input status 1
BIT0-BIT7
DI1-DI8 (ON/OFF)
1=ON; 0=OFF
BIT8 and above
System reserved
9613
258DH
Reading of external terminal input status 1
BIT0-BIT2
DO1-DO3 (HIGH/LOW)
1=LOW; 0=HIGH
BIT3
RY1 (HIGH/LOW)
1=HIGH; 0=LOW
BIT4 and above
System reserved
9614
258EH
Reading of output voltage
9615
258FH
Reading of VIF1 control terminal input value
9616
2590H
Reading of VIF2 control terminal input value
9617
2591H
Reading of VIF3 control terminal input value
9618
2592H
Reading of AOUT1 output value
9619
2593H
Reading of AOUT2 output value
9620
2594H
Reading of frequency
9621
2595H
Reading of speed
9622
2596H
Reading of active power
9623
2597H
Reading of apparent power
9624
2598H
Reading of command speed
9625
2599H
Reading of PID1 feedback value
9626
259AH
Reading of PID2 feedback value
9627
259BH
Reading of output torque
9628
259CH
Reading of excitation current
9629
259DH
Reading of torque current
9630
259EH
Reading of detecting position
9631
259FH
Reading of command torque
9632
25A0H
Reading of speed (sub PG) (option)
9633
25A1H
Reading of target frequency
9634-9699
25A2H-25E3H
System reserved
※
1
Please refer to list of alarm codes for communication with dedicated protocol.
※
2
STATUSFLAG(status flag)
Содержание SVCO6
Страница 1: ...High Performance Vector Control Inverter Instruction Manual SANKEN ELECTRIC CO LTD ...
Страница 2: ......
Страница 324: ... 322 Memorandum ...
Страница 325: ......