- 142 -
7-3
Description of Functions
●
By taking advantage of bias and gain frequencies, a common analog signal for frequency commands can be input
to more than one inverter for proportional operation.
Example) Input 0 - 10V analog signals to two inverters, so that 1st and 2nd inverters deliver output frequencies with a
ratio of 1:2 for the purpose of proportional operation.
Setting of 1st inverter: F1401=0.0(0Hz),
F1402=50.0(50Hz)
Setting of 2nd inverter: F1401=0.0(0Hz),
F1402=100.0(100Hz)
(Adjust the acceleration/deceleration time as required.)
Note 1: In negative setting frequency field, the output frequency is 0Hz.
Note 2: For PID control, the bias and gain frequencies apply to the feedback signal.
F1407
External analog input filter time
constant (VIF1)
F1408
External analog input filter time
constant (VIF2)
F1409
External analog input filter time
constant (VIF3)
Functions for setting the filter time constant of external analog signal input.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1407
F1408
F1409
External analog input filter time
constant (VIF1)
External analog input filter time
constant (VIF2)
External analog input filter time
constant (VIF3)
1-500
(set value 1=10ms)
1
(10ms)
10
10
10
If interference is detected in external analog signals, adjust the external analog input filter time constant.
Set the time constant to N × 10 ms (N = 1 to 500), the setting range is 10 to 5,000 ms.
Filters can be assigned to VIF1, VIF2 and VIF3 independently.
F1410
Set frequency gain
F1411
Analog input switching for set
frequency gain
Using an external analog input terminal, the gain is adjustable when setting frequency.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1410
Set frequency gain
0
-
100%
1%
0