- 187 -
-
187
-
C
h
ap
ter
7
7-3
Description of Functions
Multi-speed function
F2101
1st speed frequency
F2102
2nd speed frequency
F2103
3rd speed frequency
F2104
4th speed frequency
F2105
5th speed frequency
F2106
6th speed frequency
F2107
7th speed frequency
F2108
8th speed frequency
F2109
9th speed frequency
F2110
10th speed frequency
F2111
11th speed frequency
F2112
12th speed frequency
F2113
13th speed frequency
F2114
14th speed frequency
F2115
15th speed frequency
F2116
16th speed frequency
The function to set the frequency during multi-speed operation.
Code No.
Function Name
Date Content
Setting
Resolution
Factory Presets
F2101
1st speed frequency
0
-
599Hz
0.01Hz
0
F2102
2nd speed frequency
10
F2103
3rd speed frequency
20
F2104
4th speed frequency
30
F2105
5th speed frequency
40
F2106
6th speed frequency
50
F2107
7th speed frequency
60
F2108
8th speed frequency
0
F2109
9th speed frequency
0
F2110
10th speed frequency
5
F2111
11th speed frequency
15
F2112
12th speed frequency
25
F2113
13th speed frequency
35
F2114
14th speed frequency
45
F2115
15th speed frequency
55
F2116
16th speed frequency
0
●
The frequency during multi-speed operation can be selected from 1st speed to 16th speed through the combination of
control terminals 2DF, 3DF, 5DF and 9DF. According to the input status of the terminals, the inverter will run with the
selected frequency.
●
2DF, 3DF, 5DF and 9DF can be set to be an arbitrary terminal of DI1
-
DI8 through the settings of F1414
-
F1421.
●
For frequency during multi-speed operation, the new frequency can be set through the operation panel.