3) Clearing the set frequency
· Please short-circuit external control terminal T-FCL of the inverter with DCM1, 2.
Set frequency will be
cleared. And, if F1038 is set, the set frequency can be cleared when the inverter stops or turns off the
power.
Note 1:
The terminal block stepping function is used not only for setting the 1st speed frequency but also for setting
the frequencies for multiple speeds. For example, short-circuit the 2nd speed selection terminal 2DF (inverter
control terminal) and the DCM1, if the terminal block stepping increases when setting a frequency for the 2nd
speed, the set frequency for the second speed will change. But, when changing multi-segment speed during
increasing or decreasing action of the terminal block, the increasing or decreasing action of segments which
started before change will be stopped, and the increasing or decreasing action of segments after change will be
started.
Note 2:
The step function is disabled when the function lock (F1603=1, 3) is selected or at undervoltage.
Note 3:
When the terminals AD2 and AD3 are both connected to either DCM1 or DCM2 in short circuit or both left
open, the set frequency remains unchanged. (Maintain the current status)
Note 4:
The frequency setting value for the increasing or decreasing or clearing by terminal block stepping function is
determined by the current multi-speed frequency codes (F1021, F2101-F2116).
●
Others
Note: Even if F1002 = 2
-
20, 26
-
28 is selected, the frequency setting value in multi-segment speed (2nd
-
8th speed)
operation or JOG operation is still the value set by F2102
-
F2116 or F1201.
●
F1002=22: Communication
A function which sends special commands from the PC etc. to the inverter. See Chapter 7 Communication
Function for frequency setting method.
●
F1002=25: Pulse train input
The target frequency is determined with the pulse from the pulse train input by PG pulse as the 1st speed
frequency command.
The places for pulse input are A + and A- of the control circuit terminal. See 4-6-1 for terminal configuration.
Reference parameter
F1422 (Reference frequency for pulse
train input)
●
F1002 = 26, 27, 28: Analog forward / reverse run
• This function is a function which runs in the same direction with command direction at 5
-
10V and the opposite
direction to command direction at 5
-
0V based on 5V of VIF input as the center.
•·The input of each channel shall be converted into a frequency according to its bias and gain code. A negative
result is always regarded as 0.
• 5V is the bias frequency, 10V and 0V the gain frequency.
VIF analog inputs
Gain frequency
Bias frequency
10V
5
0
Forward run
Reverse run
Forward run
Forward run
Reverse run
Reverse run
(F1402, F1404, F1406)
(F1401, F1402, F1405)
Ta
rget
freq
uency
※
The operation direction of simple scheduled operation is the direction specified by the function code.
VIF analog inputs
Gain frequency
Bias frequency
10V
5
0
Forward run
Reverse run
Forward run
Forward run
Reverse run
Reverse run
(F1401, F1402, F1405)
(F1402, F1404, F1406)
Ta
rget
freq
uency