F1507
Arrival frequency
This function specifies the frequency at which a frequency arrival signal is output.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1507
Arrival frequency
0-600Hz
0.01Hz
10
If the value of any one of F1509 – F1511 is 7 (frequency arrival), the signal is output from control circuit output terminals
DO1 to DO3 when the output frequency exceeds the value of F1507.
Similarly, If the value of F1513 is 7 (frequency arrival), the signal is output from control circuit relay output terminals
FA1, FB1 or FC1 when the output frequency exceeds the value of F1507.
Output
frequency
F1508
Frequency matching range
This function specifies the out frequency band corresponding to the frequency matching signal.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1508
Frequency matching range
0-10Hz
0.01Hz
0
If the value of any one of F1509 – F1511 is 5, 6, 14 or 15, the signal is output from control circuit terminals DO1 to DO3
when the output frequency falls within the value range between ±F1508.
Similarly, for F1513, the signal is output from control circuit relay output terminals FA1, FB1 or FC1.
Note: When the frequency is specified using an analog signal, an appropriate setting should be specified using F1508 to
prevent frequency matching signal from chattering. When the vector control is active, the output frequency
constantly changes. Set F1508 to several Hz.