- 204 -
7-3
Description of Functions
The follows are function codes related to PID control.
Code No.
Function Name
Date Content
Setting
Resolution
Factory
Presets
1709
Feedback signal disconnection
detection time
0
:
only warning
0.01-199.99 second(s)
120
:
No detection
0.01s
5
3001
PID1 command value input
switching
1
:
Frequency
2
:
External analog VIF1 voltage (0-5V)
3
:
External analog VIF1 voltage (0-10V or potentiometer)
4
:
External analog VIF2 voltage (0-5V)
5
:
External analog VIF2 voltage (0-10V or potentiometer
)
6
:
External analog VIF3 voltage (0-5V)
7
:
External analog VIF3 voltage (0-10V or potentiometer)
8
:
External analog VIF1 current (4-20mA)
9
:
External analog VIF2 current (4-20mA)
10
:
External analog VIF3 current (4-20mA)
11
:
Function code setting (by F3017)
98: Pulse train input subPG(option)
99
:
Pulse train input
1
1
3002
PID1 feedback input switching 0
:
No input
1
:
External analog VIF1 voltage (0-5V)
2
:
External analog VIF1 voltage (0-10V or potentiometer)
3
:
External analog VIF2 voltage (0-5V)
4
:
External analog VIF2 voltage (0-10V or potentiometer)
5
:
External analog VIF3 voltage (0-5V)
6
:
External analog VIF3 voltage (0-10V or potentiometer)
7
:
External analog VIF1 current (4-20mA)
8
:
External analog VIF2 current (4-20mA)
9
:
External analog VIF3 current (4-20mA)
10
:
Communication mode
98: subPG feedback PID (option)
99
:
PG feedback PID
1
0
3003
PID1
control proportional gain 0-100
0.01
0.1
3004
PID1
control integral time
0.01-100 second(s)
0.01s
0.1
3005
PID1
control differential time
0-100 second(s)
0.01s
0
3006
PID1
control integral
separation judgment value
5-100% (upper frequency limit reference)
0.1%
100
3007
PID1 feedback signal input
filter time constant
1-500(set value 1=10ms)
1
10
3008
Indirect PID1 input reference
5-100%(target value reference)
0.1%
20
3009
PID1 deviation limit value
0
:
No limit
1-100%(upper frequency limit reference)
0.1%
100
3010
PID1 output limit value
0
:
No limit
1-100%(upper frequency limit reference)
0.1%
100
3011
PID1
operation polarity
switching
1
:
command value - feedback value
2
:
feedback value - command value
1
1
3012
PID1
gain polarity switching
1
:
The positive or negative deviation indicates the same gain
2
:
The positive or negative deviation indicates different gain
1
1
3013
PID1 command value gain
0-50
0.01
1
3014
PID1 feedback value gain
0-50
0.01
1
3015
PID1 control proportional gain
(negative
:
F3012=2)
0-100
0.01
0.1
3016
PID1 control integral time
(negative
:
F3012=2)
0.01-100 second(s)
0.01s
0.1
3017
PID1 control command value
0-6000
0.1
0