- 188 -
7-3
Description of Functions
Example 1) When 3rd speed is selected, the frequency set by operation panel will be stored in F2103.
Example 2) During the halfway of changing the frequency of 3rd speed operation, the output frequency of the inverter
with the speed switched to 5th speed will change to 5th speed. However, the set frequency is 3rd speed
frequency (F2103).
●
External terminals are other functions and multiplexed functions.
Example) 67
:
2DF
+
AD2
For these multiplexed terminals, the information for multi-speed operation will be only used as the terminal status of
2DF, AD2 status has no relationship with the multi-speed operation. For multi-speed switching of external terminals
and the operation status of inverter as well as F1101: when the content selected by operation command has no
relationship, it is effective.
Function Code
Frequency
2DF
3DF
5DF
9DF
F2101
1st speed
OFF
OFF
OFF
OFF
F2102
2nd speed
ON
OFF
OFF
OFF
F2103
3rd speed
OFF
ON
OFF
OFF
F2104
4th speed
ON
ON
OFF
OFF
F2105
5th speed
OFF
OFF
ON
OFF
F2106
6th speed
ON
OFF
ON
OFF
F2107
7th speed
OFF
ON
ON
OFF
F2108
8th speed
ON
ON
ON
OFF
F2109
9th speed
OFF
OFF
OFF
ON
F2110
10th speed
ON
OFF
OFF
ON
F2111
11th speed
OFF
ON
OFF
ON
F2112
12th speed
ON
ON
OFF
ON
F2113
13th speed
OFF
OFF
ON
ON
F2114
14th speed
ON
OFF
ON
ON
F2115
15th speed
OFF
ON
ON
ON
F2116
16th speed
ON
ON
ON
ON