- 107 -
C
h
ap
ter
7
-
107
-
7-3
Description of Functions
●
F1001=40: V
•
f separation control
· A function which can set the inverter‘s output frequency and output voltage independently.
· The control mode is V/f mode.
· F2001: Through V•f separation selection, you can choose complete separation or V•f proportional separation.
(
Related function codes
)
See the following function codes for details of V•f
separation function.
F2001 V•f separation function selection
F2002 V•f separation command voltage
F1002
1st speed frequency setting selection
A function for selecting the frequency setting method for the 1st speed frequency operation.
Code No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
F1002
1st speed frequency
setting selection
1: Operation panel
2: External analog VIF1 voltage (0
-
5V)
3: External analog VIF1 voltage (0
-
10V or
potentiometer)
4: External analog VIF2 voltage (0
-
5V)
5: External analog VIF2 voltage (0
-
10V or
potentiometer)
6: External analog VIF3 voltage (0
-
5V)
7: External analog VIF3 voltage (0
-
10V or
potentiometer)
8: External analog VIF1 current (4
-
20mA)
9: External analog VIF2 current (4
-
20mA)
10: External analog VIF3 current (4
-
20mA)
11: External analog VIF1 vVIF2 voltage
12: External analog VIF1 vVIF3 voltage
13: External analog VIF2 vVIF3 voltage
14: External analog VIF1 voltage -VIF2 voltage
15: External analog VIF2 voltage –VIF1 voltage
16: External analog VIF1 voltage-VIF3 voltage
17: External analog VIF3 voltage –VIF1 voltage
18: External analog VIF1 vVIF2 current
19: External analog VIF1 voltage -VIF2 current
20: External analog VIF1 current -VIF2 voltage
21: Terminal block stepping
22: Communication
25: Pulse train input
26: External analog VIF1 forward / reverse operation
(0 - 10V, 5V reference)
27: External analog VIF2 forward / reverse operation
(0 - 10V, 5V reference)
28: External analog VIF3 forward / reverse operation
(0 - 10V, 5V reference)
29: Pulse train input (subPG
:
option)
1
1
●
Reading analog frequency
A function which takes the result of calculation of the 3 channels of control circuit‘s analog input terminals VIF1,
VIF2, VIF3 (frequency command) carried out internally by the inverter as the inverter‘s command frequency.