- 141 -
C
h
ap
ter
7
7-3
Description of Functions
Input/Output-Related Function
The function blocks of input and output terminals of the inverter control circuit are described as follows.
F1401
Bias frequency (VIF1)
F1402
Gain frequency (VIF1)
F1403
Bias frequency (VIF2)
F1404
Gain frequency (VIF2)
F1405
Bias frequency (VIF3)
F1406
Gain frequency (VIF3)
In case of setting output frequency using the analog signal, these functions are used to set a frequency (bias frequency)
corresponding to minimum analog signal value (0V or 4mA) and a frequency (gain frequency) corresponding to
maximum value (5V or 10V and 20mA).
Code No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
F1401
F1403
F1405
Bias frequency (VIF1)
Bias frequency (VIF2)
Bias frequency (VIF3)
0-±600Hz
(frequency at 0V or 4mA)
In case of negative value, -XXX.X will be
displayed.
0.1Hz
0
0
0
F1402
F1404
F1406
Gain frequency (VIF1)
Gain frequency (VIF2)
Gain frequency (VIF3)
0-±600Hz
(frequency at 5V or 10V or 20 m)
In case of negative value, -XXXX will be
displayed.
0.1Hz
60
60
60
The relation between the analog frequency setting signal (VIF1-VIF3) and the inverter output frequency is shown as
follows.
Output
frequency
Analog frequency
setting signal
Setting example: When F1401 =- 10.0 (-10Hz), F1402 = 90.0 (90 Hz), and F1002 = 3 (frequency setting VIF1: 0 - 10V),
the output frequency is as shown below.
Output
frequency
(Measure against noise: Do not use a signal of less than 1V.)
Analog frequency setting signal
Gain frequency
Bias frequency