- 311 -
-
3
1
1
-
C
h
ap
ter
1
1
11-1 Standard Specification
Item
Specification
Model(SVC06-□□□□-
4)
0900
1100
1320
1600
1850
2000
2200
2500
O
u
tp
u
t
spec
ifi
ca
ti
o
n
Mode A
Heavy
overload
Standard applicable motor [kW]
90
110
132
160
185
200
220
250
Rated capacity [kVA] *1
120
146
175
211
249
267
295
327
Rated current [A] *2
173
211
253
304
360
386
426
472
Overload current rating *3
150%-1min
Output frequency range *4
0.05-400Hz(Starting frequency 0.05-60Hz variable)
Mode B
Light
overload
Standard applicable motor [kW]
110
132
160
200
220
250
280
315
Rated capacity [kVA] *1
146
180
211
267
295
327
374
409
Rated current [A] *2
211
253
304
386
426
472
540
590
Overload current rating *3
120%-1min
Output frequency range *4
0.05-200Hz(Starting frequency 0.05-60Hz variable)
Rated output voltage *5
3
φ
380V-460V
Inp
u
t
p
o
w
er
sup
p
ly
Voltage & Frequency
3
φ
380V-460V, 50/60Hz
Allowable fluctuation
Voltage: -15%, +10% Frequency: ±5% Voltage unbalance: within 3%
Power supply impedance
1% and above(Use optional reactor if less than 1%)
Mode A
Heavy
overload
Required power capacity [kVA] *6
120
146
180
211
249
267
295
327
Input current
[A] *7
With DCL
161
196
235
283
335
359
396
439
Without DCL
Mode B
Light
overload
Required power capacity [kVA]*6
146
180
211
267
295
327
374
409
Input current
[A] *7
With DCL
196
235
283
359
396
439
502
549
Without DCL
Protective structure
Totally enclosed(IP20)
Cooling method
Forced air cooling
Approximate weight
62kg
110kg
140kg
Carrier frequency
Sine wave PWM(carrier frequency 1k
-
8kHz) *8
DC reactor
Standard(External)
*1
Rated capacity at the output voltage of 400V
*2
When input voltage is AC400V and above, the rated current will be decreased according to the output power
*3
One minute is allowed every 10 minutes
*4
During vector control, PG sensorless is 0.25Hz
-
240Hz /PG sensor is 0.05Hz
-
240Hz (depends on the number of poles)
*5
Output voltage cannot exceed power supply voltage
*6
Vary with the impedance changes of the power supply including a DC reactor
*7
Vary with the impedance of the power supply
*8
The maximum value of carrier frequency varies with the inverter capacity mode and operation status.