- 170 -
7-3
Description of Functions
F1605
Quick knob long-pressing cancel
selection
This function is used to select continuous pressing action of the on operation panel in function code display mode.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1605
Quick knob long-pressing
cancel selection
0: Long pressing cancel disabled
1: Long-pressing cancel enabled
1
0
●
When F1605=1, the same operation with can be made by continuous pressing action of in function code
display mode.
Note 1: In status display mode, frequency setting B is selected regardless of the setting of F1605. See ―5-3-4 Frequency
input‖ for long pressing of key in status display mode.
Note 2: When setting F1605 = 1 and F1606 = 2 or F1606 = 3 at the same time, the ―Set‖ action or ―Cancel‖ action of the
function code setting value varies depending on the duration time (length) for which the key is pressed.
Please give full attention to avoid misoperation.
Reference parameter:
F1606 (Function code value setting key selection)
F1606
Function code value setting key selection
This function is used to select the key for confirming the set value of a function code.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1606
Function code value setting
key selection
1: Set key
2: Press the quick knob
3: Press the set key or quick knob
1
1
●
Set F1606 = 2 or F1606 = 3, the function code value can be set by pressing .
Note 1: When setting F1605 = 1 and
F1606 = 2 or F1606 = 3 at the same time, the ―Set‖ action or ―Cancel‖ action of the function code setting value
varies depending on the duration time for which the key is pressed. Please give full attention to avoid
misoperation.
Reference parameter
F1605 (Quick knob long-pressing cancel selection)
F1607
Target frequency setting time-out
This function is used to set the time for auto returning to the status display when frequency setting B is not in operation.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1607
Target frequency setting
time-out
0: Timeout disabled
1-60 sec.
1 s
5
When F1607=0 is set, the state of frequency setting B will continue until is pressed.