- 164 -
7-3
Description of Functions
The converted value of inverter output frequency and current output is shown as follows:
When the inverter output frequency ×F1515 (current output multiple) = 0.3Hz, the frequency output = 4mA.
When the inverter output frequency ×F1515 (current output multiple) = 120Hz, the frequency output = 20mA.
Current output multiple may be changed in function code F1515, please make appropriate adjustment based on service
condition.
*
Adjust the maximum output frequency to 20mA
or below.
Adjust the impedance of current output load side to 500Ω or below. In case of large impedance, the current output shall be
20mA or below.
When the current output makes output frequency=0 Hz, multiple=0, please output the minimum value 4mA.
Make sure that there is no wiring short-circuit and open circuit at load side before current output.
The signal wire may not work correctly due to short-circuit or open circuit.
F1516
Torque matching level
F1517
Torque matching range
These functions are used to set torque level and torque matching range output by the torque matching signal. This
function is active in vector control mode.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1516
Torque matching level
0
-
±200%
0.1%
100
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1517
Torque matching range
0
-
50%
0.1%
25
If any one of F1509 – F1511 is 42 (Torque matching signal), the signal is output from control circuit output terminals
DO1 to DO3 when the output torque matches the set value. The matching range is specified with the set value of F1517.
Similarly, for F1513, the signal can also be output from control circuit relay output terminals FA1, FB1 or FC1
Inverter output frequency [Hz]
×
Current output multiple F1515
Current
Output
[mA]