- 268 -
7-4 Serial Communication Function
OP—CD
Example of communication data (when inverter number is 1)
Transmission from computer to inverter
Transmission from inverter to computer
N
·
Writing of function code data
·
Writing 50Hz to F1008 ―lower frequency
limit‖
HD IN OP
DT
SUM EM
* 0 1 N 1 0 0 8 0 5 0 0 0 SUM
CR or
CR+LF
·
Writing of OK
HD
IN
OP
DT
SUM
EM
*
0
1
N
e
F
F
F
0
SUM
CR or
CR+LF
·
Interference error(Example: interference with F4007)
HD
IN
OP
DT
SUM
EM
*
0
1
N
e
4
0
0
7
SUM
CR or
CR+LF
·
Setting error(error code)
HD
IN
OP
DT
SUM
EM
*
0
1
N
e
F
F
F
5
SUM
CR or
CR+LF
·
See list of error codes for details of error code.
·
See ―Note‖ for the written data format of F5001 (motor
poles, voltage and capacity).
O
·
Setting of the frequency
·
Set the target frequency to 55Hz
HD
IN
OP
DT
SUM EM
*
0 1 O 0 5 5 0 0 SUM
CR or
CR+LF
·
Set the frequency data by a multiple of 100
·
Same as for code data write
HD
IN
OP
ST
SUM
EM
*
0
1
O
e
F
F
F
0
SUM
CR or
CR+LF
·
―eFFFA‖ is returned if the frequency setting is not permitted.
P
·
Forward run command
HD
IN
OP
SUM
EM
*
0
1
P
SUM
CR or
CR+LF
HD
IN
OP
ST
SUM
EM
*
0
1
P
ST
SUM
CR or
CR+LF
*ST
:
―0‖
:
Normal
―1‖
:
Operation control is not permitted
―2‖
:
No operation in alarm status
Q
·
Reverse run command
HD
IN
OP
SUM
EM
*
0
1
Q
SUM
CR or
CR+LF
HD
IN
OP
ST
SUM
EM
*
0
1
Q
ST
SUM
CR or
CR+LF
*ST
:
―0‖
:
Normal
―1‖
:
Operation control is not permitted
―2‖
:
No operation in alarm status
R
·
Stop command
HD
IN
OP
SUM
EM
*
0
1
R
SUM
CR or
CR+LF
HD
IN
OP
ST
SUM
EM
*
0
1
R
ST
SUM
CR or
CR+LF
*ST
:
―0‖
:
Normal
―1‖
:
Operation control is not permitted
S
·
Alarm reset
HD
IN
OP
SUM
EM
*
0
1
S
SUM
CR or
CR+LF
HD
IN
OP
SUM
EM
*
0
1
S
SUM
CR or
CR+LF