Appendix A
Data Conversion
480
Correction related the number of digits for numeral display
In the conversion of the data between a conventional and a new model, conver-
sion is executed in the manner shown below due to differences in the range of
numeric values that can be displayed.
Difference
New models:
A numeric value of up to 10 digits can be displayed.
Conventional models:
A numeric value of up to 8 digits can be displayed.
Conversion result, error message and corrective action
Status before
Conversion
Status after
Conversion
Error Message
Corrective Action
With a new model,
a numeral display
element for which a
numeric value ex-
ceeding 8 digits is
displayed is regis-
tered to the symbol
manager.
With a conventional
model, a numeral
display element of
greater than 8 digits
is discarded.
Numeral Display:
Total number of in-
teger and decimal
exceeds limit. It is
discarded.
Create a new numeral
display element. Correct
the screen data or the
program at the host so
that a constant of up to
8 digits suffices. (Refer
to 6-6 Numeral Display.)
Correction related to analogue meter
In the conversion of the data between new models (with “-V1” and above) and
other PT models, conversion is executed in the manner shown below due to
presence/absence of analogue meter.
Difference
New models (with “-V1” and above):
Analogue meter can be used.
Conventional models, new models (below “-V1”):
Analogue meter cannot be used.
Conversion result, error message and corrective action
Status before
Conversion
Status after
Conversion
Error Message
Corrective Action
With a new model
(“-V1” and above),
an analogue meter
is registered to the
symbol manager.
With a conventional
model and a new
model (below
“-V1”), an analogue
meter is not dis-
played.
Cannot paste ana-
logue meter. It is
discarded.
Create a bar graph or
other display element
instead of an analogue
meter to display con-
tents that was displayed
by an analogue meter.
Correction related to control touch switch of trend graph
In the conversion of the data between a conventional and a new model, conver-
sion is executed in the manner shown below due to differences in the trend graph
control touch switches.
Difference
New models:
Marks with codes FFEF to FFF5 (hexadecimal) are
used as trend graph control touch switches.
Conventional models:
No trend graph control touch switches (codes FFEF
to FFF5 may be used as desired).
Содержание NT - SUPPORT TOOL FOR WINDOWS V4
Страница 1: ...Support Tool for Windows Ver 4 Cat No V061 E1 05 NT series OPERATION MANUAL...
Страница 2: ...NT series Support Tool for Windows Ver 4 j Operation Manual Revised May 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 353: ...8 2 Section Library Editor 341 Double clicking the control menu box of the library editor Control menu box...