646
37 FUNCTIONS
37.4 System Consistency Check
SD memory card
The system consistency check is performed to check the installation of the SD memory cards and the status of the write
protect switch. The SD memory card type or capacity is not checked.
The system checks if the SD memory card is inserted while the control system is running even in the case
only the standby system is turned off and on or reset. When an SD memory card is used, removing it more
than necessary is not recommended.
Operation of when a mismatch is detected
If a mismatch of the installation of the SD memory cards or the status of the write protect switch is detected, a stop error
occurs on the standby system CPU module. If a mismatch is detected when the CPU modules of both systems are
simultaneously turned on or reset, a stop error occurs on the control system CPU module as well.
Safety operation mode
Whether the safety operation modes (SAFETY MODE/TEST MODE) of the CPU modules of both systems are the same is
checked.
Operation of when a mismatch is detected
If a mismatch is detected between the safety operation modes, a continuation error occurs on the standby system CPU
module.
The BACKUP LEDs of the redundant function modules of the control system and standby system flash because a cause of
the system switching failure has occurred.
Backup mode setting
When "Do Not Check" is set in "Operating Status Check", a continuation error is not detected for the standby system CPU
module even if the safety operation modes are different between the both systems.
[CPU Parameter]
[Redundant System Settings]
[Redundant Behavior Setting]
[Backup Mode Setting]
Window
Displayed items
Item
Description
Setting range
Default
Safety Operation Mode Check
Set whether to perform the consistency check for the
safety operation modes of both systems or not.
• Do Not Check
• Check
Check
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......