342
21 DEVICES
21.3 User Device
■
Long timer (LT/LST)
In the following program, the accuracy of Tp (the time duration from the long timer coil activation to long timer contact
activation) is (Ts-Tu)
Tp < (Ts + Tu).
(1) Cp is updated.
(2) LT0 is initialized to 0.
(3) The result of (Ct - Cp) is added.: 0 + (12 - 10) = 2
(4) The result of (Ct - Cp) is added.: 2 + (13 - 12) = 3
(5) The result of (Ct - Cp) is added.: 3 + (15 - 13) = 5
Tp: time duration from the long timer coil activation to long timer contact activation
Ts: setting value of the long timer
Tu: time limit value of the long timer
M1
M0
K5
LT0
LT0
ON
ON
10
11
12
13
14
10
12
0
2
15
13
3
15
5
ON
ON
16
17
(1)
(2)
(3)
(4)
(5)
(1)
(1)
M0
LT0 (coil)
LT0 (contact)
M1
Previous count value
of LT0 (Cp)
Current value of LT0
Counter used in system
(Ct)
LT0 coil
Execution of
(OUT LT0 instruction)
M1 coil
Execution of
(OUT M1 instruction)
Process value of LT0 (Tp)
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......