Appendix 5 List of Special Register Areas
835
A
SD53
AC/DC DOWN
The number of
AC/DC DOWN
detections
The value of this register increments by one and stored as a BIN code, each
time input voltage drops to 85% (AC power)/65% (DC power) or less of the
nominal value while the CPU module is carrying out an operation. A counting
cycle from 0 to 65535 to 0 is repeated.
S (Error)
ALL
SD60
Number of
module with
blown fuse
Number of
module with
blown fuse
The lowest number of module in which a fuse blew is stored.
S (Error)
ALL
SD61
I/O module verify
error module
number
I/O module verify
error module
number
The lowest I/O number of the module which has an error detected by the I/O
module verification is stored.
S (Error)
ALL
SD62
Annunciator
number
Annunciator
number
The annunciator number which is detected first is stored.
S (Instruction
execution)
ALL
SD63
Number of
annunciators
Number of
annunciators
The number of detected annunciator is stored.
S (Instruction
execution)
ALL
SD64 to
SD79
Table of detected
annunciator
numbers
Detected
annunciator
number
• Numbers of activated annunciators are sequentially registered into SD64
to SD79, each time an annunciator (F) is turned on by the SET F
instruction.
• Number of the annunciator deactivated by the RST F instruction is
removed from register areas SD64 to SD79, and the numbers of
annunciators which were lined up behind the removed one move forward
one by one. When the number of detected annunciators has already
reached 16, the number of a newly detected annunciator is not stored into
SD64 to SD79.
For details on the annunciator, refer to the annunciator (F) (
S (Instruction
execution)
ALL
SD80
Detailed
information 1
information
category
Detailed
information 1
information
category code
• Detailed information 1 information category code is stored.
b0 to b7: Information category code
b8 to b15: Unused (fixed to 0)
• The following codes are stored into the information category code.
0: N/A
1: program position information
2: drive number and file name
4: Parameter information
5: System configuration information
6: number of times information
7: time information
24: Failure information
27: System switching information
34: Continuous RUN prevention setting in TEST MODE
37: Data type (tracking transfer) information
38: Tracking transfer trigger information
46: CPU module data backup/restoration folder information
50: Safety station system configuration information
S (Error)
ALL
No.
Name
Data stored
Details
Set by
(setting
timing)
CPU
b15
b7
b8
b0
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......