158
10 TEST FUNCTION
10.2 Device test with execution conditions
Operation when device test with execution conditions is registered
The device test with execution conditions can forcibly change device/label values (status) of specified locations.
Specify a location of a device/label value (status) to be changed with a program name and a step number. In addition, specify
a device/label and its value (status) to be changed with a device/label name and a setting value.
Changes made to the device/label value (status) take effect in the specified step and later. However, when the device/label
value (status) is changed due to operations of the program or other factors in the specified step and later, the device/label
value (status) is changed accordingly.
In the device test with execution conditions, a device/label value is changed in a specified step regardless of whether or not
the instruction execution conditions are satisfied in the specified step. In the following example, the D0 value is changed to 35
regardless of the status (on/off) of M0.
Operation when device test with execution conditions is disabled
The device/label value (status) when the registration is disabled is held. (It is not returned to the value (status) before
execution of the device test with execution conditions.)
(1) The device test with execution conditions that sets D0 to 35 and is executed before execution of the instruction is registered to the step (100).
(2) The device value in the specified step is changed regardless of the value (on/off) of M0.
OFF
ON
D0
M0
10
35
+
K10
(1)
D0
M0
(100)
(2)
CPU module operation
Program
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......