APPX
Appendix 9 Processing Time
917
A
When the file format is binary file
■
When a global device or global label is specified
The following table lists the collection intervals at which data can be collected under the following conditions.
• Scan time = 1.5ms (up to 3ms)
*1
• Internal buffer capacity setting = 128K bytes per setting (default setting)
• Collection setting = Time specification (data collection at time interval)
• Data setting = Data register (D) (Data-type: word-signed (decimal number type))
• Output setting = Day/time column (output format is default) and index column are outputted.
• Save setting = file switching timing: 1024K bytes (when the data storage destination memory is the function memory) or
10000 records (when the data storage destination memory is the SD memory card), operation when the number of saved
files exceeded: overwriting
• When the data storage destination memory is the SD memory card, functions that require access to files in the SD memory
card except for the data logging function are not active.
• The default setting value is used for the file transfer server setting of the CPU Module Logging Configuration Tool (however,
the IP address, login user name, and password can be customized).
• Parameters are used only for required settings that can be connected to the FTP server (IP address settings of the module
parameter only) and default setting values are used for other settings.
*1 3ms (to 4.5ms) for the Process CPU (redundant mode)
Number of points
File transfer
Collection interval at which data can be collected
When the
function
memory is
used
When the SD memory card is used
NZ1MEM-2GBSD
NZ1MEM-4/8/16GBSD
Programmable
controller CPU
Process CPU,
Safety CPU
Programmable
controller CPU
Process CPU,
Safety CPU
8
points
(8 points
1
setting)
Not performed
1.0ms
1.0ms
1.0ms
1.0ms
Performed
No file deletion
specification at
transfer
completion
1.0ms
1.0ms
File deletion
specification at
transfer
completion
1.0ms
1.0ms
1.0ms
16
points
(16 points
1
setting)
Not performed
1.0ms
1.0ms
1.0ms
2.0ms
Performed
No file deletion
specification at
transfer
completion
1.0ms
1.0ms
File deletion
specification at
transfer
completion
1.0ms
1.0ms
1.0ms
64
points
(64 points
1
setting)
Not performed
1.0ms
2.0ms
1.0ms
5.0ms
Performed
No file deletion
specification at
transfer
completion
1.0ms
1.0ms
File deletion
specification at
transfer
completion
1.0ms
1.0ms
2.0ms
(For the
R04(EN)CPU:
1.0ms)
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...