Appendix 1 Error Codes
2520H
Invalid interrupt
• Even though an interrupt was
requested, there is no interrupt
factor.
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, or module (I/O module or
intelligent function module) connected.
Please consult your local Mitsubishi
representative.
System
configuration
information
At interrupt
occurrence
2521H
2522H
Invalid interrupt
• An interrupt was requested from
the module with no interrupt
pointer setting.
Stop
• Check and correct the interrupt pointer
setting in the module parameters.
• Take measures so that no interrupt is
requested from the module with no
interrupt pointer setting.
• Check and correct the interrupt setting
in the buffer memory of the intelligent
function module.
• Correct the BASIC program executed
in the QD51.
System
configuration
information
At interrupt
occurrence
2610H
Inter-module
synchronization
signal error
• An execution interval error of the
synchronization interrupt program
has been detected.
• An inter-module synchronization
error has been detected.
Stop/
continue
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, extension cable, or module
(I/O module or intelligent function
module) connected. Please consult
your local Mitsubishi representative.
Always
2611H
• An inter-module synchronization
error has been detected.
Stop
System
configuration
information
At power-on,
at RESET, at
END
instruction
execution
2630H
Multiple CPU
synchronization
signal error
• An execution interval error of the
synchronization interrupt program
has been detected.
• A multiple CPU synchronization
error has been detected.
Stop/
continue
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or base unit. Please consult your local
Mitsubishi representative.
Always
2631H
• A multiple CPU synchronization
error has been detected.
Stop
System
configuration
information
At power-on,
at RESET, at
END
instruction
execution
2800H
I/O number or
network number
specification
error
• The specified I/O number is out of
range (other than 0 to FFH, 3E0 to
3E3H).
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Error location
information
At instruction
execution
2801H
• The I/O number of the module that
does not exist was specified.
Stop/
continue
Error location
information,
system
configuration
information
At instruction
execution
2802H
I/O number or
network number
specification
error
• The I/O number of the module that
does not support the instruction
was specified.
• The dedicated instruction
specified in the program cannot
be executed in the specified
module or mode.
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Check the execution propriety
(including support status and execution
mode) of the dedicated instruction,
referring to the manual for the target
module.
Error location
information,
system
configuration
information
At instruction
execution
2803H
I/O number or
network number
specification
error
• The I/O number of the module that
cannot be specified in the
instruction was specified.
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Error location
information,
system
configuration
information
At instruction
execution
2804H
• The specified network number is
out of range (other than 1 to 239).
2805H
• The network number that does not
exist was specified.
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......