21 DEVICES
21.3 User Device
339
21
■
Retentive timer (ST)
This device counts the sum of time duration in which the coil is turned on. When the retentive timer coil is turned on,
measurement starts and when the timer current value matches a setting value (when time is up), the retentive timer contact is
turned on. The current value and the contact on/off state is retained even when the retentive timer coil is turned off. When the
coil is turned on again, measurement starts with the retained current value. To clear the retentive timer current value and turn
off the contact, issue the RST ST
instruction.
■
Long retentive timer (LST)
This device counts the sum of time duration in which the coil is turned on. When the long retentive timer coil is turned on,
measurement starts and when the timer current value matches a setting value (when time is up), the contact is turned on. The
current value and the contact on/off state is retained even when the long retentive timer coil is turned off. When the coil is
turned on again, measurement starts with the retained current value. To clear the long retentive timer current value and turn
off the contact, issue the RST LST
instruction.
The long retentive timer (LST) can be used in interrupt programs. (
(1) Even though the coil (1)) turns off, the current value is held.
(2) Even though the coil (1)) turns off, the contact remains on.
(1) Even though the coil turns off, the current value is held.
(2) Even though the coil turns off, the contact remains on.
0
0
1 … 150
150
151 … 199
200
X0
X0
X1
K200
ST0
ST0
ST0
Y10
RST
OFF
OFF
OFF
ON
ON
(1)
(2)
1)
3)
2)
Instruction execution
RST ST0
instruction (3))
Contact of
ST0 (2))
Current value of
ST0
Coil of ST0 (1))
15 seconds
5 seconds
0
1 … 150
150
151 … 199
200
0
ON
ON
OFF
X0
OFF
OFF
1.5ms
0.5ms
(2)
(1)
Coil of LST0
Current value
of LST0
Contact of
LST0
RST LST0
instruction
Instruction execution
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......