![Mitsubishi Electric MELSEC iQ-R-R00CPU Скачать руководство пользователя страница 727](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-r00cpu/melsec-iq-r-r00cpu_user-manual_239139727.webp)
APPX
Appendix 1 Error Codes
725
A
2221H
Parameter error
• The set value is out of range.
Stop
• Check the detailed information
(parameter information) of the error by
executing module diagnostics using
the engineering tool and correct the
parameter setting corresponding to the
displayed number. If the same error
code is displayed again, the possible
cause is a hardware failure of the data
memory in the CPU module, memory
card, or module (SIL2 function module,
safety function module, I/O module, or
intelligent function module) connected.
Please consult your local Mitsubishi
representative.
Parameter
information
At power-on,
at RESET, at
STOP
RUN
state, at END
instruction
execution, at
instruction
execution, at
module
access
An unsupported parameter exists.
• Other than 1 is set to the group
number in the CC-Link IEF Basic
setting.
Stop
Check the CPU module version and use
the supported product.
Use the product in a supported category.
• Set the number of occupied stations so
that the total number is 16 stations or
less, and set 1 to the group number.
Parameter
information
At power-on,
at RESET, at
STOP
RUN
state, at END
instruction
execution, at
instruction
execution, at
module
access
2222H
Parameter error
• Use of the function that is not
supported by the module is
enabled in parameter.
Stop
• Check the detailed information
(parameter information) of the error by
executing module diagnostics using
the engineering tool and correct the
parameter setting corresponding to the
displayed number. If the same error
code is displayed again, the possible
cause is a hardware failure of the data
memory in the CPU module, memory
card, or module (SIL2 function module,
safety function module, I/O module, or
intelligent function module) connected.
Please consult your local Mitsubishi
representative.
Parameter
information
At power-on,
at RESET, at
STOP
RUN
state
2223H
Parameter error
• The parameter that needs a reset
of the CPU module was modified
and overwritten.
Stop
• Reset the CPU module and run it
again.
Parameter
information
At write, at
power-on, at
RESET, at
STOP
RUN
state
2224H
Parameter error
• A memory area cannot be
ensured.
• A global label setting file exists
when the label assignment area
set in the CPU parameters is 0K
word.
Stop
• Check the detailed information
(parameter information) of the error by
executing module diagnostics using
the engineering tool, display the error-
detected area by clicking the [Error
Jump] button, and increase the
capacity of the area. (If the capacity of
the area cannot be increased,
decrease the capacity of other areas.)
• Reduce the number of labels or local
devices used.
• If no global label is used, delete the
global label setting file.
Parameter
information
At write, at
power-on, at
RESET, at
STOP
RUN
state
2225H
Parameter error
• The CPU module model set to the
project using the engineering tool
differs from that of the CPU
module actually mounted.
• The operation set in the memory
card parameters cannot be
performed.
(The boot function cannot be
executed.)
Stop
• Correct the CPU module model set to
the project in accordance with the CPU
module actually mounted.
• Delete the memory card parameter
settings.
• Remove the memory card so that the
operation set in the memory card
parameters will not be performed. (Do
not execute the boot operation.)
Parameter
information
At write, at
power-on, at
RESET, at
STOP
RUN
state
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......