764
APPX
Appendix 1 Error Codes
4072H
Verification error
• The global label setting file or the program file with the target
program name differs from the one when the file was written.
Or, the file was deleted.
• Write the global label setting file or the program file with the
target program name.
• Write the file again. (Read the file that is read from the CPU
module using CPU Module Logging Configuration Tool, and
write it again using CPU Module Logging Configuration
Tool.)
• Check and correct the SD940 setting.
4080H
Any other error
• Request data error
■
When CPU Module Logging Configuration Tool is used
• Request or setting data error
• Check the request data that has been specified.
■
When CPU Module Logging Configuration Tool is used
• Check the specified data, and write it to the CPU module
again.
4081H
Any other error
• The search target data cannot be detected.
• Check the data to be searched.
4082H
Any other error
• The specified command cannot be executed because it is
being executed.
• Execute the command again after the processing of the
command from another engineering tool ends.
4083H
Any other error
• An attempt was made to perform operation to the program
not registered in parameter.
■
When CPU Module Logging Configuration Tool is used
• The data logging specifying the program that is stored in the
CPU module but not registered in the CPU parameters was
started.
• Register the program in parameter.
4084H
Any other error
• The specified pointer (P or I) does not exist.
• Check if the pointer (P or I) exist in the data.
4085H
Any other error
• The pointer (P or I) cannot be specified because the
program is not specified in parameter.
• Register the program to be executed in parameter first, and
specify the pointer (P or I).
4086H
Any other error
• The specified pointer (P or I) has already been added.
• Check and correct the pointer number to be added.
4087H
Any other error
• The number of pointers (P or I) exceeds its limit.
• Check and correct the specified pointer (P or I).
4088H
Any other error
• The specified step number is not at the head of the
instruction.
• The program differs from that stored in the CPU module.
■
When CPU Module Logging Configuration Tool is used
• The data logging specifying the step number that does not
exist or is not specified as the start number of the instruction
was started.
• Check and correct the specified step number.
• Read the program from the CPU module to match it with that
of the engineering tool, and then execute online change
again.
4089H
Any other error
• An attempt was made to insert/delete the END instruction by
online program change.
• Check the specified program file contents.
• Set the operating status of the CPU module to STOP, and
write the program.
408AH
Any other error
• The file capacity exceeded after the online change was
executed.
• Check the capacity of the specified program file.
• Set the operating status of the CPU module to STOP, and
write the program.
408BH
Any other error
• The remote request cannot be executed.
• Change the status of the CPU module so that the remote
request can be executed, and execute the request again.
• For remote operation, set the parameter to "Enable remote
reset".
408DH
Any other error
• The instruction code that cannot be handled exists.
• Check whether the model of the used CPU module is correct
or not.
• The program where online change was attempted includes
the instruction that cannot be handled by the CPU module
specified for the project. Check the program and delete the
instruction.
408EH
Any other error
• The write step is illegal.
• The program differs from that stored in the CPU module.
• Set the operating status of the CPU module to STOP, and
write the program.
• The starting position of online program change is not
specified with the correct program step number. Check
whether the engineering tool supports the model and version
of the CPU module that is specified for the project.
• Read the program from the CPU module to match it with that
of the engineering tool, and then execute online the program
change again.
40A0H
SFC device
specification
error
• A block No. outside the range was specified.
• Check the setting and correct it.
40A1H
SFC device
specification
error
• The number of blocks exceeds the range.
• Check the set quantity and correct it.
Error
code
Error name
Error details and cause
Action
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......