292
16 MULTIPLE CPU SYSTEM FUNCTION
16.2 Operation Settings
Applicable errors to the stop setting
The following table lists the applicable errors to the setting that specifies the operation of all the CPU modules of when a major
or moderate error has occurred in any of the CPU modules.
Synchronous startup setting
Startup time is synchronized among the CPU modules. This setting eliminates the need for an interlock program that monitors
the startup time of another CPU module when accessing it. Note, however, that the startup of the entire system delays
because the system starts up with the last CPU module.
[System Parameter]
[Multiple CPU Setting]
[Operation Mode Setting]
[Synchronous Startup Setting]
Window
Displayed items
• Group setting for the synchronized start-up is available. For example, a setting in which only CPUs No.1
and No.2 start synchronously within a multiple CPU system with four CPU modules is possible.
• If a reserved (empty) CPU is specified to synchronize, it is skipped and the other CPUs in the group start
synchronously.
• This setting is designed to access to each CPU module without interlock in the multiple CPU system. It is
not intended to be used for starting operation processing at the same time across CPU modules after
startup.
Error name
Error code
Another CPU module moderate error
1220H
Another CPU module major error
2461H, 2462H, 2470H
Item
Description
Setting range
Default
PLC No. 1
Set the CPU modules whose startup time is synchronized in
the multiple CPU system.
• Synchronize
• Do not Synchronize
Synchronize
PLC No. 2
PLC No. 3
PLC No. 4
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......